Tyco PowerSeries Neo TL280LE Mode D'emploi page 6

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Communicator Receiver/Panel
Receiver
3G2080(R)E
LE2080(R)
TL2803G(R)E
TL280LE(R)
TL280(R)E
Panel
NOTE: Enter [*][8][Installer Code][900] at keypad to view the panel version number.
Encryption
The communicator uses 128 Bit AES encryption. Encryption can only be enabled from the monitoring station receiver. Each
receiver (Ethernet 1 and 2, Cellular 1 and 2) can independently have encryption enabled or disabled. When encryption is
enabled, the central station will configure the device to encrypt communications the next time the communicator module per-
forms a communication to that receiver.
NOTE: Packets will start being encrypted only after the next event is sent to that receiver, or if the unit is restarted.
Before leaving the installation site, the communicator TL2803(R)E / TL280LE(R) Ethernet line shall be connected via
an APPROVED (acceptable to the local authorities) Network Interface Device (NID). All wiring shall be performed
according to the local electrical codes.
This alarm communicator shall be installed by service persons only (service person is defined as a person having the appro-
priate technical training and experience necessary to be aware of hazards to which that person may be exposed to in per-
forming a task and can also take measures to minimize the risks to that person or other persons). The Communicator shall
be installed and used within an environment that provides the pollution degree max 2, overvoltages category II, in non- haz-
ardous, indoor locations only. This manual shall be used with the installation manual of the panel which is connected to the
communicator. All instructions specified within the panel manual must be observed.
All the local rules imposed by local electrical codes shall be observed and respected during installation.
Installing the Ethernet Cable (TLXXXX Models Only)
A Category 5 (CAT 5) Ethernet cable must be run from a source with Internet connectivity to the communicator module,
inside the panel. The communicator end of the cable must be terminated with an RJ45 plug, which will connect to the com-
municator's RJ45 jack after the communicator is installed. All requirements for installation of CAT5 Ethernet cable must be
observed for correct operation of the communicator, including, but not limited to, the following:
Do NOT strip off cable sheathing more than required for proper termination.
l
Do NOT kink/knot cable.
l
Do NOT crush cable with cable ties.
l
Do NOT untwist CAT5 pairs more than ½ in. (1.2cm).
l
Do NOT splice cable.
l
Do NOT bend cable at right angles or make any other sharp bends.
l
NOTE: CAT5 specification requires that any cable bend must have a minimum 2 in. (5 cm) bend radius. Maximum length of
CAT 5 cable is 328 ft. (100 m).
Table 2: Compatible Receivers and Panels
Sur-Gard System I-IP Receiver, version 1.13+
l
Sur-Gard System II Receiver, version 2.10+
l
Sur-Gard SG-DRL3-IP, version 2.30+ (for Sur-Gard System III Receiver)
l
Sur-Gard SG-DRL4-IP version 1.20+ (for Sur-Gard System IV Receiver)
l
Sur-Gard SG-DRL5-IP version 1.00+ (for Sur-Gard System 5 Receiver)
l
HS2016
l
HS2016-4
l
HS2032
l
HS2064
l
HS2128
l
Pre Installation Configuration
Communicator Installation Configuration
Description
6

Publicité

Table des Matières
loading

Table des Matières