For EN50131- 1 compliant installations, the following programming options shall be set as described. Supervision Heart-
beat (required for ATS4 and ATS5):
[851][004]
set to 0087h (135s heartbeat).
l
NOTE: The compatible receiver at ARC location shall have supervision window programmed for 1800s (ATS4) or 180s
(ATS5) for the primary communications path, which can be Ethernet receiver 1 or cellular receiver 1, depending
on the product you are installing.
[851][107]
Set to 0087h (135s Heartbeat) for Ethernet Receiver 1
l
[851][207]
Set to 0087h (135s Heartbeat) for Cellular Receiver 1
l
[851][100]
Options 1 and 2 shall be enabled if using Ethernet Receiver 1 as the primary path
l
[851][200]
Options 1 and 2 shall be enabled if using Cellular Receiver 1 as the primary path
l
Configuration of communication paths (all ATS classes)
[300][001]
select option 02 for auto routing (this will allow transmission of the events over all available communication
l
paths in the system)
[380]
enable option 5 (YES) for parallel transmission over all available communication paths (if redundant con-
l
figuration is desired)
[382]
enable option 5 (YES) to enable Alternate communicator
l
[384]
enable the desired back-up configuration (receiver 2 back-up for receiver 1 or receiver 3 back-up for receiver 1)
l
Model
Power Supply Ratings
Input Voltage
Current Consumption
Standby Current
Alarm (Transmitting)
Current
Operating Frequency
Typical Antenna Gain
Environmental Specifications
Operating Temperature
Humidity
Mechanical Specifications
Board Dimensions (mm)
Weight (grams) with
bracket
EN50131-1 Installation Requirements
Ratings Compatibility
Table 1: Communicator Ratings
3G2080(R)E/LE2080(R)
Cellular only
Power is supplied from the panel's PC-Link header or a PCL-422 module in
remote cabinet installations. In remote cabinet installations, the PCL-422 module
located with the communicator is powered by either an HSM2204 or an HSM2300.
Refer to the PCL-422 installation instructions for details.
90mA
850MHz, 900MHz, 1800MHz, 1900MHz, 2100MHz
5% ~ 93% relative humidity, non-condensing
100 × 150 × 15
310
TL280(R)E
Internet only
10.8-12.5 VDC
100mA
400mA
2dBi
-10°C to 55°C (0°C to 49°C for UL/ULC)
100 x 150 x 15
300
5
TL2803G(R)E/TL280LE(R)
Internet and Cellular
120mA
100 × 150 × 15
320