2.
The HSPA3GCellular path is immune to conducted and radiated RF fields
with levels up to 10V/mas tested per EN50130- 4 Standard.
3.
The TL2803G(R)E-EU/3G2080(R)E-EU/TL280(R)E module conforms with
radiated emissions levels for Class B equipment as per standards
EN61000- 6-3/EN55022/CISPR22.
4.
The TL2803G(R)E-EU/3G2080(R)E-EU/TL280(R)E module uses AES128
encryption and heartbeat supervision for HSPA3G Cellular communication
paths and it meets security levels S2 asper EN50136-2:2013. It also uses
authentication for each message exchanged with the compatible receiver
equipment at ARC and it meets levelI2 for information security.
5.
The 3G2080(R)E-EU module has only one communication path:
HSPA3GCellularcommunication path using 900/1800/2100MHz Public
Cellular Network. The HSPA3GCellularcommunication path that can be
used in a standalone mode in conjunction with a DSC alarm system(com-
patible DSC alarm control panel models: HS2128/064/032/016). The sup-
ported ATS configuration is: custom category C.
6.
The TL280(R)E module has only one communication path: Ethernet com-
munication path using Internet. The communication path that can be used
in a standalone mode in conjunction with a DSC alarm system(compatible
DSC alarm control panel models: HS2128/064/032/016). The supported
ATSconfiguration is: customcategory C.
7.
The TL2803G(R)E-EU module has two communication paths: HSPA3G
Cellular communication path using 900/1800/2100MHz Public Cellular Net-
work and Ethernet communication path using Internet. The communication
path scan be used in a standalone mode in conjunction with a DSC
alarmsystem(compatible DSC alarm control panelmodels:
HS2128/064/032/016). The supported ATS configuration is: custom
category C.
8.
TL2803G(R)E-EU/3G2080(R)E-EU/TL280(R)E has been tested for com-
pliance in conjunction with the following applicable standards: EN50136-
1:2012, EN50136- 2:2013, EN50131-10:2014, ATS configuration: C.
For EN50131- 1:2006/A1:2009 compliant installations, the following programming
options shall be set as described.
Supervision Heartbeat: shall be set to 180 seconds
NOTE: The compatible receiver at ARC location shall have supervision window
programmed for 180 seconds. TL2803G(R)E-EU/3G2080 (R)E- EU/TL280(R) E
has been certified by TELEFICATION in accordance with EN50131- 1:2006/
A1:2009, EN50131-10:2014 requirements for Grade 2, Class II and
EN50136-2:2013 Configuration: C
ATS Custom Category C
EN50136-1:2012 Annex D Table D.1
EN50136-1:2012 Annex D Table D.2
EN50136-1:2012 Annex D Table D.3
EN50136-1:2012 Annex D Table D.4
EN50136-1:2012 Annex D Table D.5
EN50136-1:2012 Annex D Table D.6
EN50136-1:2012 Table 1
EN50136-1:2012 Table 4
EN50136-1:2012 Table 5
EN50136-1:2012 Table 6
EN50136-2:2013 Table 1
EN50136-2:2013 Table 2
EN50136-2:2013 Table 3
SIMPLIFIED EU DECLARATION OF CONFORMITY
Hereby, Tyco Safety Products Canada Ltd declares that the radio equipment type
is in compliance with Directive 2014/53/EU. The full text of the EU declarations
of conformity for the models mentioned below are available at the following
internet addresses:
TL2803G(R)E-EU - http://dsc.com/pdf/1605003
3G2080(R)E- EU - http://dsc.com/pdf/1605004
Frequency Band
EGSM900 890.0MHz- 914.8MHz
EGSM900 880.2MHz-889.8MHz
DCS1800 1710.2MHz-1784.8MHz
WCDMA (Band
VIII) 882.4MHz
912.6MHz
Level
D3
M3
T4
A4 (Depending on cellular carrierused)
S2
(use
AES-
128
authentication/sequentialinformation in
each message transmitted to the SG
receiver)
I2 (use AES-128 encryption)
Use single communication path for
models 3G2080 (R) E- EU (cellular
network), TL280 (R) E (Ethernet port)
and two communication pathsfor model
TL2803G(R)E-EU (cell/Ethernet).
ATSfailure reported to ARC
ATS failure reported to AS (DSC
compatible
control
HS2128/HS2064/HS2032/HS2016)
There is no recording of availability
failure
No logging function provided
No memory provided for logging
function
ATSfailure reported to ARC
Maximum Power
Class 4 (2W)@ 900MHz, GSM
Class 1(1W)@ 1800MHz, GSM
Class E2 (0.5W)@ 900MHz, EDGE
-
Class E2 (0.4W)@ 1800MHz, EDGE
WCDMA2100 (Band I) 1922.4MHz -
1977.6MHz
Only models TL2803GRE-EU, TL2803GE- EU, 3G2080RE-EU, 3G2080E-EU are
CE compliant.
European single point of contact: Tyco Safety Products, Voltaweg 20, 6101 XK
Echt, Netherlands
UL/ULC Installation Requirements
NOTE: For equipment used at the protected premises and intended to facilitate IP
communications (hubs, routers,
cable modems), 24 hour backup power is required. Where such cannot be
facilitated, a secondary(back-up) communication channel is required.
Domain Name Service (DNS) programming is not permitted in UL1610
listed systems.
Technical Specifications
The input voltage to the Communicator can be drawn from the Underwriters Lab-
oratories/Underwriters Laboratories Canada (UL/ULC) listed control panel.
Notes for using Private, Corporate, and High Speed Data Networks:
Network access and domain access policies shall be set to restrict unauthorized
network access, and spoofing or Denial of Service (DoS) attacks. Select an
Internet Service Provider(ISP) that has redundant servers/systems, back-up power,
routers with firewalls enabled, and methods to identify and protect against DoS
attacks (e.g., via spoofing).
Notes for using Public Switched and Cellular Data Networks:
Communication channels shall be facilitated such that the communicator will restrict
unauthorized access, which could otherwise compromise security. The com-
municator shall be located in a secured area.
• For ULC Residential Fire and Burglary applications the TL2803G (R)
E/3G2080(R)E/TL280(R)E/LE2080(R)/TL280LE(R) can be used as primary com-
munication channel via either cellular or Ethernet or as a back-up in conjunction
with the Digital Alarm Communicator Transmitter (DACT). Test transmission
every 24 hours shall be enabled on each channel.
• For ULC Commercial Fire and Burglary applications the TL2803G (R)
E/3G2080(R) E/TL280(R) E/LE2080 (R)/TL280LE(R) can be used as a passive
communication module with the following security levels:
P1 (each channel cellular or Ethernet is independent)
l
P2 (cellular and Ethernet in back-up configuration, panel section [851][005]
l
toggle option [5] OFF).
P3 (cellular and Ethernet in redundant configuration, panel section [851]
l
[5] toggle option [5] ON).
The communicator can also be used as an active communication system with
the security levels A1-A4 (each channel cellular or Ethernet independent or
together in a back-up/redundant configuration). For active line security systems
AES128 bit encryption shall be enabled (at the monitoring station receiver) and
and
the supervision heartbeat rate shall be set as 90 seconds (panel section [851]
[004] = 005A/90). The supervision window at the Signal Receiver Center(SRC)'s
receiver shall be programmed as maximum of 180 (00B4/180) seconds.
NOTE: For ULC commercial fire passive communication, encryption shall be
enabled,
• For UL Residential Fire and Burglary applications the TL2803G (R)
E/3G2080R/TL280(R)E/LE2080(R)/TL280LE(R) can be used as the primary com-
munication channel via either cellular or Ethernet, or as a back- up in conjunction
with the DACT (30 day test transmission is required on each channel).
• For UL Commercial Burglary applications the TL2803G(R) E/ 3G2080R /
TL280(R)E / LE2080(R) / TL280LE(R) can be used as dual signalling line com-
munication system (cellular and Ethernet channels used in redundant con-
figuration), standard line security and as encrypted line security.
panel
• The supervision heartbeat shall be enabled (panel section [851][005] toggle
option [1] (Ethernet) and/or toggle option [2] (cellular) shall be ON), toggle option
[3] (supervision type) shall be ON and the supervision heartbeat rate shall be
selected as 135 (0087/135) seconds. Option [004] = 0087. The supervision
window at the supervising station shall be maximum200 (00C8/200) seconds. For
encrypted line security systems the encryption AES128 bit shall be enabled at the
monitoring station receiver.
• For UL Commercial Burglary installations, the TL2803G(R) E/3G2080 (R)
E/TL280(R)E/LE2080 (R)/TL280LE(R) is listed asa primary (sole) communication
means(heartbeat must be enabled) or for supplementary (back- up) use in con-
junction with a Plain Old Telephone Service (POTS) line dialer. When the heartbeat
transmission over the Ethernet orcellular networkis enabled, using the TL2803G
(R) E/3G2080 (R) E/TL280 (R) E with a compatible control unit listed for stand-
ard/encrypted line security, it can provide line security for the alarm system over
the primary line.
• The TL2803G(R)E/3G2080(R)E/TL280(R)E/LE2080(R)/TL280LE(R) is also suit-
able to be used with a compatible control unit listed for dual line security trans-
mission when used in conjunction with a DACT or a Public Switched Data
Network (PSDN) transmitter, where the PSDN provides the line security and is
the primary line. In this mode, alarm signals are required to be sent
simultaneously over both communication methods.
19
Class 3 (0.25W) @ 900/2100MHz,
WCDMA
NIDs, Digital
Subscriber Line (DSL),