7 - CONTROL
Secondary statuses
Circuit 1
Address
Id
Description
1
Current H2O set point
4500
4501
2
Return H2O operating temperature
4502
3
Supply H2O operating temperature
4
Averaged temperature variation
4503
4504
5
Instantaneous temperature variation
4505
64
Statuses and alarms bitmap
4506
7
Circulator
8
Valve position (calculated)
4507
4508
9
PID output calculation
4509
10
Valve request correction
11
Correction scan timer
4510
4511
12
Valve relay activation duration
4512
13
Dew operating temperature
14
Air operating temperature
4513
4514
15
Operating R.H.
4515-
Free
4529
U:M:
°C*10
Setpoint
°C*10
Temperature probe
°C*10
Temperature probe
°C*10
Temperature Delta
°C*10
Temperature Delta
Bitmap
Bit
Function
Circulator
0
1
Anti-lock
2
Valve in full recirculation (or full
open) position
3
In posizionamento tutto ricircolo (o in
tutto aperto)
Anti-ice
4
5
Circulator pump forcing due to
compressor start-up
6
Set point limited by dew point
7
Call
8
Supply temperature beyond limits
9
Circulator pump thermal alarm
10
Defective return probe
Defective supply probe
11
12
Antifreeze alarm
13
Secondary on/of
Free
14
15
Free
%*10 (0...1000)
Circulator
%*10 (0...1000)
-1000...1000
%*10 (-100...100)
Sec
Sec
°C*10
°C*10
%
Notes
Configuration
1=On
1=Function running
1=Positioned
1=In positioning
1=under way
1=under way
1=active
1=In energy request mode
1=active
1 =on / 0=off
62