7 - CONTROL
According to the unit configuration some parameters are visible and some not.
Supervision controls
Address
Description
U.M.
RemoteMode
Bitmap
2600
2601
FlagRegister 1
Bitmap
MODBUS PROTOCOL - INSTALLER USE
Bit
Function
0
1=ON / 0=OFF
1=Maintenance / 0=OFF
1
2
1=Heat / 0=Cool
3
Eco
4
DHW only mode
5
Request DHW
DHW priority
6
7
Free
Anti-frost condition
8
9
Room thermoregulation
request
10
Active solar
Free
11
12
Only boiler
13
Free
14
Free
Free
15
Bit
Function
0
EnSetPointRete
1
EnSetSanitariaRete
2
EnModoRete
EnRichiestaACSRete
3
4
EnModoSoloACSRete
5
EnStatoRete
6
EnPriorACSRete
EnSondaMandataRete
7
EnSondaRipresaRete
8
9
EnSondaAccumuloRete
10
EnSondaAriaRete
11
EnSondaMandataAuxRete
12
Free
EnSondaTExtRete
13
14
Free
15
EnDemandLimitRete
Note
Enable
EnStatoRete = 1
ON/OFF via network (1=Comfort; 0=OFF)
enabled when EnStatoRete=1
EnStatoRete = 1
Maintenance via network (1=maintenance)
enabled when EnStatoRete=1
EnModoRete = 1
Machine mode via network (1=Heat, 0=Cool )
enabled when EnModoRete=1
EnStatoRete = 1
Economy via network (1=Eco) enabled when
EnStatoRete=1
EnModoSoloACSRete = 1
1 = DHW only mode via network, enabled if
EnModoSoloACSRete=1
EnRichiestaACSRete = 1
1 = DHW request via network, enabled if
EnRichiestaACSRete = 1
EnPriorACSRete = 1
1= DHW priority active if EnPriorACSRete = 1
1= anti-frost condition active
EnRichiestaAmbRete = 1
1= room thermoregulation active, enabled if
EnRichiestaAmbRete = 1
1= active solar
EnSoloCaldaiaRete = 1
1= boiler only operation, enabled if
EnSoloCaldaiaRete = 1
Enable
Remote water setpoint enable
Remote DHW setpoint enable
Season settings via network
Remote unit mode enable
DHW request via network
Remote DHW request enable
DHW only via network
Remote DHW only enable
On, Off, Maintenance via
Remote unit state enable
network
DHW/circuit priority via
Remote DHW priority enable
network
Remote delivery water temperature enable
Remote return water temperature enable
Remote storage tank temperature enable
0: on-board reading
Remote room air temperature enable
(thermostat).
1: networked sensor reading
Remote auxiliary delivery water temperature
enable
Remote external temperature sensor enable
Demand limit value via
Remote demand limit value enable
network
Note
Note
55