5 - ELECTRICAL CONNECTIONS
5.10 - SUPERVISOR (option)
The unit can be connected to an external supervisor system.
In this case follow the connections as shown.
CONNECTIONS
N° of
Section
2
Ref.
connection
(mm
cables
Min
Max
2 twisted
RS485
0,22
0,35
and shielded
Recommended cable Belden 3105A or others with equal
properties
Configuration:
parameter
description
Extended description
Adress
ModBus supervision serial address
315
BaudRate
Baud Rate (0=4800 / 1=9600 2=19200)
316
supervision serial
Parity
Parity 0=NO / 1=Odd 2=Even
317
supervision serial
To use Sphera in a MODBUS network it is necessary to
address the RS-485 MODULE by S3, S4, S5 ; allowed and
valid addresses from 1 to 127
S5 - it sets the address hundreds :
ON = 100, OFF = 0
S3 - it sets the address dozens
S4 - it sets the address units
S1 - 485 terminator : ON = termination YES
S2 - line polarizer
Inside the 485 network must be polarized only one
board, usually is polarized tha master, i.e. the PC; in
this case S2 = OFF
= polarization NO
If more cards are polarized, faults occur
J1 - RS 485 serial
J3 - TTL serial
*
The unit parameters are overwritten by RCW15 remote keyboard. Make the customization by using RCW15
Nominal
Impedance
Recommended
)
capacity
characteristics
cable
pF/m
BELDEN
<50
120
3105A
LV = green led :
ok
LR = red led quick flashing:
wrong address
faulty module
Example address 49:
Example address 120:
5.11 -
RCW15 REMOTE CONTROL WITH TOUCH SCREEN
DISPLAY, FOR BUILT-IN INSTALLATION (BOX 503) OR
FOR WALL INSTALLATION.
Remote user keypad, to control the unit main functions.
To use the keyboard, you need:
power supply 12Vdc AL12X (supplied separately)
For details, see instructions accessory.
29