7 - START-UP
6.13 - SCREED HEATING
Only with radiant panels
Procedure to follow in the event of winter mode start-up in
cold environments and screed to be heated or a new non-dry
screed.
1. Close the heads
2. Leave only one area active
3. Start the unit with the ACS enabled
4. Wait for the area to reach the temperature
5. Repeat steps 2 and 3 for each area
Starting all the areas simultaneously can block the unit.
Do not start the system during the winter in rooms without
fittings.
6.14 - PERSONALIZATION OF THE SYSTEM
WATER SET POINT
Set the setpoint for the boosters.
Configurazione:
Parameter Description
Extended description
SetCool
Summer Set Point
51
52
SetHeat
Winter Set Point
SecondSetC
Summer secondary SetPoint
53
54
SecondSetH
Winter secondary SetPoint
SetCoolC2
Summer Set Point circuit 2
55
56
SetHeatC2
Winter Set Point circuit 2
59
SecondSetC2
Summer secondary SetPoint circuit 2
60
SecondSetH2
Winter secondary SetPoint circuit 2
Settings
Parameter
*
The unit parameters are overwritten by RCW15 remote keyboard. Make the customization by using RCW15
6.15 SYSTEM WATER CLIMATIC CURVES
Set point compensation on outdoor temperature
Summer
With outside low temperatures the refrigerant requirements are
reduced. The internal comfort can also be obtained with a set-
point higher than standard. The correction is added to the set-
point (increased with the decrease in temperature).
Winter
With outside mild temperatures the thermal requirements are
reduced.
The internal comfort can also be obtained with a lower set-
point.
The correction is subtracted from the set-point (increased with
the decrease in temperature).
Example:
if outside temperature (T. Ext.) > 114, set water = par 52 -117
Summer
Configuration :
parameter
description
R1
R2
112
120
Ext. temp. min. summer correction
113
121
Outdoor temp. max. summer correction
114
122
Ext. temp. max. winter correction
115
123
Ext. temp. min. winter correction
116
124
Summer correction max. value
117
125
Winter correction max. value
parameter description
Extended description
Enabling of compensation on ext.
CompExt
Temp. 0=No ;1=only in Cool; 2=only in
4
Heat; 3=Always
Settings
Parame-
ter
Winter
External T. correction
34