Flowmatic S option
The configuration of Flowmatic S depends on your order.
The regeneration air control is configured at the factory and
does not require any further adjustment.
Target value control: The process air is set via the
"Venti.Proz." potentiometer or an external target value.
Actual value control: Enter the desired target value at the
Flowmatic S (▲ / ▼). For this purpose, keep changing the
value until the desired value is shown on the display. The
Flowmatic S will now adjust the value until the fan has reached
its maximum speed.
29
Setting the target value:
Setting the actual value:
The default values are additionally indicated on a label attached
to the Flowmatic S.
The settings for the actual value can be made in the
Flowmatic S menu:
Note
If "Base Setup" is displayed, you have browsed too far
through the menu. Press the "ESC" button in this case.
1. Press both buttons ▲ / ▼ simultaneously. The
"INFO" menu will be displayed.
2. Press the ▼ button until the "SETTING" menu is displayed.
3. Press the "P" button.
4. Press the ▼ button until the "SETPOINT 1" menu is
displayed.
5. Press the "P" button. The indication flashes.
6. Use the buttons ▲ / ▼ to reduce or increase the set value
as desired.
7. Finally press the "P" button to save the settings for the
new target value.
desiccant dehumidifier TTR 2000 / TTR 2800 / TTR 3700
The upper "Venti.Proz." potentiometer
serves to define the target value for the
process/dry air volume in m
The topmost point roughly marks the
regulated nominal air volume and the
point in the middle marks the nominal
air volume in emergency operation.
The points indicate the rough settings for
emergency operation (failure of
Flowmatic S).
3
/h.
EN