Error codes
01
If this code is displayed, it means that the cabinet temperature sensor has a short
circuit. In the meantime, the cabinet itself will try to maintain the set temperature. The
sensor must be replaced. Request service assistance.
02
If this code is displayed, it means that the cabinet temperature sensor has been
broken. In the meantime, the cabinet itself will try to maintain the set temperature.
The sensor must be replaced. Request service assistance.
03
If this code is displayed, it means that the evaporator temperature sensor has a short
circuit. It means that defrosting of the evaporator will be interrupted. The sensor must
be replaced. Request service assistance.
04
If this code is displayed, it means that the evaporator temperature sensor has been
broken. It means that defrosting of the evaporator will be interrupted. The sensor
must be replaced. Request service assistance.
07
If this code is displayed, it means that the humidity sensor has a short circuit. It
means that humidifying will be interrupted. The sensor must be replaced. Request
service assistance.
08
If this code is displayed, it means that the humidity sensor has been broken. It means
that humidifying will be interrupted. The sensor must be replaced. Request service
assistance.
23
Temperature alarm. The temperature monitoring is factory-set to +/- 10°C relative to
the setpoint. The alarm is triggered, if the upper or lower limit is exceeded.
40
Steam generator system alarm. This means that an error has occurred in the steam
generator system. Request service assistance.
By pushing the P key, it is possible to view the errors that may have occurred.
If several errors have appeared, they are shown as F1, F2, etc., - the display
alternates between this indication and the actual error code. (Only when the cabinet
is in stand-by mode).
"clr" is displayed to indicate, if you want to confirm / ignore the error(s).
To confirm / ignore the errors, push the + key. To retain the error indications, push
the – key.
Power failure
During power failure, the control unit remembers all entered program settings and the clock
continues to run. The program therefore proceeds as if nothing had happened.