Application area
LFV200 is a point level sensor with tuning fork
for point level detection.
It is designed for industrial use in all areas of
process technology and is used in liquids.
Function monitoring
The electronics module of LFV200 continuously
monitors the following criteria via frequency
evaluation:
Strong corrosion or damage on the tuning
fork
Loss of vibration
Line break to the piezo drive
If a malfunction is detected or in case of power
failure, the electronics takes on a defined
switching condition, i.e. the output is open (safe
state).
Functional principle
The tuning fork is piezoelectrically energised
and vibrates at its mechanical resonance
frequency of approx. 1100 Hz. When the tuning
fork is submerged in the product, the frequency
changes. This change is detected by the integ-
rated electronics module and converted into a
switching command.
2.3

Storage and transport

Packaging
Your instrument was protected by packaging
during transport. Its capacity to handle normal
loads during transport is assured by a test
based on ISO 4180.
The packaging consists of cardboard. This
material is environment-friendly and recyclable.
Dispose of the packaging material via specia-
lised recycling companies.
LFV200 • IO-Link
3

Mounting

3.1

General instructions

Switching point
Generally, LFV200 can be mounted in any posi-
tion. Just install the instrument so that the tuning
fork is at the height of the requested switching
point. Keep in mind that the switching point can
vary depending on the installation position.
The switching point refers to the medium water
(1 g/cm³/0.036 lbs/in³). Please keep in mind that
the switching point of the instrument shifts when
the medium has a density differing from water.
2
1
3
Abb. 27: Vertical mounting
1
Switching point in water
2
Switching point with lower density
3
Switching point with higher density
1
2
Abb. 28: Horizontal mounting
1
Switching point
2
Switching point (recommended mounting position,
particularly for adhesive products)
3 Mounting
13