8 Supplement
Ʋ Red
Output variable
Output signal
Max. ohmic load (R
)
A
Switching output
Switching current (C/Q1)
Switching voltage
Voltage supply
Operating voltage
Power consumption
Short-circuit resistance
Reverse voltage protection
Residual ripple
Domestic current requirement
Electrical protective measures
Protection rating
Ʋ M12 x 1 plug connection
Overvoltage category
Protection class
8.2

Dimensions

Abb. 51: LFV200 with M12 x 1 plug connection
18
Fault
IO-Link with transistor output PNP
≤ 0.5 kΩ
C/Q1: PNP; IO-Link
100 mA
≥ operating voltage (L+) -2.7 V DC
18 ... 30 V DC
max. 0.5 W
Q1, Q2 against M
L+ against L-
≤ 1.3 V
of 0 Hz ... 100 kHz
ss
approx. 10 mA
IP 66/IP 67 (NEMA Type 4X) or IP 66/IP 68 (1 bar)
NEMA Type 6P
III
II
M12 x 1
ø 31,7 mm
(1.25")
SW 32 mm
(1.26")
G
1
/
,
1
/
NPT
2
2
G
3
/
,
3
/
NPT
4
4
G 1 , 1 NPT
LFV200 • IO-Link