The AVR controls the generator voltage. The AVR is
used to keep a constant voltage when the load and
machine parameters vary.
The AVR requires a so-called sensing connection; a
power supply from a specific circuit (AUX); an output to
the rotor (+/-).
In case of unbalanced or distorted load, voltage
regulation accuracy could be reduced.
A frequency control progressively reduces the generator
excitation when the drive engine speed drops below a
pre-set, adjustable threshold preventing over-excitation
at low operating speeds and abating the load engage
effects on the engine.
In conclusion the regulator reaction time can be
modulated to eliminate any voltage instability that may
arise.
The output voltage can be changed by adjusting
potentiometer "V". Run the generating set to its nominal
speed and turn until the required voltage is obtained.
If a small variation in speed causes a change in
voltage, then the under speed protection should first be
calibrated.
The voltage sensing jumper should be connected:
• to terminals "115" if connected to a voltage between
100 and 130V
• to terminals "230" if connected to a voltage between
185 and 245V.
• to terminals "400" if connected to a voltage between
340 and 460V.
• to terminals "480" if connected to a voltage between
440 and 520V.
If the voltage is set any higher than its
maximum limit the generator may be
damaged.
WARNING!
Stability adjustment: if on load voltage fluctuations
are experienced adjust potentiometer "ST", which
modulates the reaction time of the regulator to external
inputs, thereby eliminating any instability in the
alternator-load system.
If the adjustment via potentiometer ST does not prove
to be sufficient, is possible also to use the dip-switch
ST+ / ST: moving it to the ON position (ST +) stability
increases.
Setting of the under speed protection at 50 (60)
Hz: start up rotation of the generating set adjusting it to
obtain a frequency of 46 (56)Hz. Turn trimmer "UF" until
the voltage begins to drop. Restore nominal speed.
If the under speed is set at too low
a frequency, the generator may be
damaged. On the other hand, too high a
frequency can cause voltage drops with
WARNING!
high loads.
Remote voltages adjustment : wire the potentiometer
(5kOhm, 3W) to the shorted terminals "EXT POT". Run
the generating set to its nominal speed and adjust the
external potentiometer and eventually also the trimmer
24
"V" to obtain the required voltage.
Remote voltages adjustment :
1) with potentiometer:
Turn ON the dip-switch EXT-
POT (and make sure the dip switches EXT-VOLT is
turned OFF).
Wire the potentiometer (5kOhm, 3W) to the terminals
"EXT POT". Run the generating set to its nominal speed
and adjust the external potentiometer and trimmer "V" to
obtain the desired voltage. The external potentiometer
has the effect of increasing the voltage value set by the
"V" trimmer.
2) Connection with controller or cosf regulator:
ON the dip-switch EXT-VOLT (and make sure the dip
switches EXT-POT is turned OFF). The AVR regulator
accepts voltage analogic input (0-10VDC, observe
polarity shown in figure) for remote voltage adjustment.
To set the system, follow this procedure:
- Decrease the voltage by turning the "V" trimmer
counter-clockwise;
- Apply half the control voltage at the "EXT pot" terminals
(5 VDC);
- Act on the "V" trimmer to bring the voltage to the
nominal value;
in this way, the external controller can increase or
decrease the output voltage.
In case the remote voltage adjustment is not used, turn
OFF the dip-switches EXT-POT and EXT-VOLT. Pay
attention not to turn ON both the dip-switches.
V ST UF
Phase
Frequency
Dip-switch
Dip-switch
V ST UF
A
B
V ST UF
Off
On
CW
Voltage
Increase
A
A
B
V
CCW
Voltage
Off
Off
Decrease
On
V ST UF
On
CW
Voltage
Voltage
Increase
CW
Stability
CW
increasing
Voltage
V
Decrease
CCW
Voltage
Increase
Decrease
ST
CCW
Stability
V
Voltage
CCW
Voltage
Increase
decreasing
Decrease
CW
Stability
Off
Decrease
On
Underfrequency
ST
CCW
Stability
protection limit
Corner
CW
Increase
increasing
CW
Frequency
CW
Stability
Voltage
Increase
Increase
Decrease
Corner
CW
Underfrequency
Corner
V
UF
CCW
CCW
Voltage
Frequency
Frequency
protection limit
ST
CCW
Decrease
Increase
Stability
Decrease
decreasing
Corner
Increase
UF
CCW
Frequency
Decrease
CW
Stability
Decrease
Corner
CW
ST
CCW
Stability
Frequency
Increase
Increase
Corner
UF
CCW
Frequency
Corner
CW
Frequency
Decrease
Increase
Corner
UF
CCW
Frequency
Decrease
Turn
Off
On
V ST UF
Voltage
Dip-switch
Off
On
Off
-
+
L
On
C
N
A
B
Off
On
Polarity of EXT. Voltage
CW
Voltage
-
+
-
Increase
+
L
B
C
N
L
C
N
Off
V
CCW
Off
Voltage
On
Decrease
On
Polarity of EXT. Voltage
0V (-)
Polarity of EXT. Voltage
Stability
CW
Stability
decreasing
0-10V (+)
Decrease
Off
On
ST
CCW
-
Stability
+
Stability
Off
L
A
B
C
N
Increase
increasing
0V (-)
On
0-10V (+)
Connection with controller,
Observe polarity:
Corner
CW
Polarity of EXT. Voltage
0V (-)
Frequency
0-10V (+)
Increase
Corner
UF
CCW
Off
Frequency
On
Decrease
0V (-)
0-10V (+)
Off
On
-
+
C
Polari
Off
On
0V
0-10V