Adjustment; Restricting Vertical Vents; Venturi Adjustment; Pilot Burner Adjustment - Napoleon Bayfield GDS25N-1 Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

8.0 adjustment

EN
8.1

restricting vertical vents

Vertical installations may display a very active flame. Loosen the two screws and slide the restrictor plate blocking the
exhaust path. This reduces the velocity of the exhaust gases, slowing down the flame pattern and creating a more
traditional flame appearance. For vertical vents greater than 15 ft (5m), this restrictor must be fully closed.
RESTRICTOR SHOWN IN A
FULLY OPEN POSITION
8.2

venturi adjustment

This appliance has an air shutter that has been factory set open according to
the chart below:
Regardless of venturi orientation, closing the air shutter will cause a more
yellow flame, but can lead to carbonization. Opening the air shutter will cause
a more blue flame, but can cause flame lifting from the burner ports. The flame
may not appear yellow immediately; allow 15 to 30 minutes for the final flame
colour to be established.
AIR SHUTTER ADJUSTMENT MUST ONLY BE DONE BY A QUALIFIED
INSTALLER!
note:
It is important that the orifice is securely inserted into the venturi.
Remove the 2 screws securing the burner. Air shutters have been factory
set open according to the Venturi Adjustment Chart. These settings are for
(maximum) horizontal termination. Adjustment may be required depending
on fuel type, vent configuration and altitude. After making adjustments
replace the burner ensuring that the venturi tube
fits over the orifice and replace the screws.
8.3

pilot burner adjustment

Adjust the pilot screw to provide properly sized fl ame. Turn in a clockwise direction to reduce the gas fl ow.
Check Pressure Readings:
Inlet pressure can be checked by turning screw (A) counter-
clockwise 2 or 3 turns and then placing pressure gauge tubing
over the test point. Gauge should read as described on the chart
below. Check pressure with main burner operating on "HI".
Outlet pressure can be checked the same as above using screw
(B). Gauge should read as described on the chart below. Check
pressure with main burner operating on "HI".
After taking pressure readings, be sure to turn screws
clockwise fi rmly to reseal. Do not overtorque.
Leak test with a soap and water solution.
Prior to pilot adjustment, ensure that the pilot assembly has not been painted. If overspray or painting of
the pilot assembly has occurred remove the paint from the pilot assembly, or replace. Fine emery cloth or a
36
synthetic scrub pad (such as Scotch-Brite™) can be used to remove the paint from the pilot hood, electrode
W415-2207 / C / 08.23.18
and flame sensor.
Pressure
Natural Gas
Natural Gas
RESTRICTOR SHOWN IN A
FULLY CLOSED POSITION
VENTURI
BURNER
ORIFICE
33.1
VENTURI ADJUSTMENT CHART
FUEL
NG
P
7/16" (11mm)
B
A
INSERT PILOT ASSEMBLY
PILOT SCREW
B
A
Propane
Propane
AIR
SHUTTER
OPENING
GDS25-1
5/16" (8mm)

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Bayfield gds25p-1

Table des Matières