Johnson Controls tyco 3G4000W Manuel D'utilisation page 28

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

To use the SMS command and control feature, in the Command and Control Access Code field,
enter up to 8 digits to create an access code. You need to include the access code in the SMS you
send to the 3G4000W communicator when performing various functions.
[332] – SMS Phone Number 1: Default (Blank)
The 3G4000W communicator only processes command and control SMS messages when they are
sent from a known cell phone number. Program the user's cell phone number into this field to
provide the phone access to execute command and control functions.
[333] – SMS Phone Number 2: Default (Blank)
The 3G4000W communicator only processes command and control SMS messages when they are
sent from a known cell phone number. Program the user's cell phone number into this field to
provide the phone access to execute command and control functions.
[334] – SMS Phone Number 3: Default (Blank)
The 3G4000W communicator only processes command and control SMS messages when they are
sent from a known cell phone number. Program the user's cell phone number into this field to
provide the phone access to execute command and control functions.
[335] – SMS Phone Number 4: Default (Blank)
The 3G4000W communicator only processes command and control SMS messages when they are
sent from a known cell phone number. Program the user's cell phone number into this field to
provide the phone access to execute command and control functions.
[336] – SMS Phone Number 5: Default (Blank)
The 3G4000W communicator only processes command and control SMS messages when they are
sent from a known cell phone number. Program the user's cell phone number into this field to
provide the phone access to execute command and control functions.
[337] – SMS Phone Number 6: Default (Blank)
The 3G4000W communicator only processes command and control SMS messages when they are
sent from a known cell phone number. Program the user's cell phone number into this field to
provide the phone access to execute command and control functions.
[345] – [5] – PTM Force Dial Enabled: Default (Disabled)
If the 3G4000W communicator is being used in backup mode, and panel transmission monitoring
is desired, enable this option if the control panel is configured for force dialing. Force dialing is
an option in many security panels that causes the system to dial out even if there is no dial tone
present. The 3G4000W counts a number of failed panel communication attempts and determines
if the maximum error count has been reached. In order to maintain an accurate count, this option
needs to be enabled so any failed communication attempt made by the control panel registers as
an error and increases the PTM error count by 1.
[364] – PTM Call Duration: Default (3 minutes)
This setting determines how long the 3G4000W communciator seizes control of the phone line
and provides dialtone, handshake and kissoff frequencies to the control panel for SIA or Contact
ID communications. This setting only applies when the 3G4000W communciator is configured as a
backup communicator and the PTM error count has been reached.
[347] – PTM Max Errors Before Takeover: Default (4)
This section determines how many failed panel PSTN communication attempts must occur before
the 3G4000W communciator seizes the phone line connection and provides the required dial
28
3G4000W 3G (HSPA) WIRELESS ALARM COMMUNICATOR INSTALLATION MANUAL 5.0

Publicité

Table des Matières
loading

Table des Matières