Receiver options tab

Up to 4 cellular receivers can be programmed for central station communications. Each can have
a unique, panel-dialed phone number associated with them for use with the panel transmission
monitoring feature.
Cellular Receiver Supervision – This option determines if the communicator sends supervision
heartbeat signals to the receiver to monitor whether the path is functional. Supervision troubles are
detected and indicated if the path is not functional. If supervision is not required, this option should
be disabled.
Account Code – The system account code identifies the communicator to the central station
receiver, so the monitoring station can determine the account and address of the system. Up to 10
digits can be programmed for the receiver account code, and different account codes may be used
for each of the 4 receivers.
DNIS – A DNIS value can be used in conjunction with the account code to access different profiles in
a SurGard System 5 receiver. Up to 5 digits can be programmed for the DNIS and each receiver can
have a different DNIS value.
Receiver IP – Program an IPv4 IP address for the central station receiver in this section, using the
format XXX.XXX.XXX.XXX. If the receiver domain name feature is used, the IP address programmed
in this section is ignored.
APN – The access point name required for the communicator must match the SIM card being used
in order to allow data sessions to be used with the product.
Note: For best practice use the same APN for the public APN and the Receiver 1-4 APNs.
Remote Port – Program the port associated with the central station receiver in this section.
Receiver Test Transmission Reporting Code – This entry is used to enable or disable the test
transmission reporting code. Enter 00 to disable or FF to allow the automatic test transmission
reporting codes to be used.
Receiver Initialization Status – When the 3G4000W communicator is reprogrammed or boots
up, it initializes with the central station receiver. The status of this operation is displayed here.
The cell in DLS shows Failed if the 3G4000W communicator could not reach the programmed
receiver or Initialized when successful. This field shows Initialization Not Started if the receiver is
not programmed or if the 3G4000W communicator has not attempted to connect to the receiver
yet.
Receiver Encrypted – The 3G4000W communicator can be configured for encrypted central station
communications using 128 bit AES encryption. This operation requires a central station receiver
that supports encryption. This field indicates whether the receiver communications are presently
encrypted or not.

PTM options tab

Up to 4 phone numbers can be programmed for use with the 3G4000W's panel transmission
monitoring feature. Enter each phone number that should be monitored and enable it in each of
these sections. The phone number dialed by the panel must be 5 digits or more. Refer to the panel
transmission monitoring feature description for more information.
Note: If the control panel is configured to communicate signals to more than one central
station receiver, best practice requires that every receiver phone number dialed by the panel
be included in the PTM phone number programming sections.