13.4 FLOW
LIMIT
Navigation
Home > Settings > FLOW
LIMIT
FLOW
LIMIT
Enable FLOW
function
LIMIT
Set FLOW
.
LIMIT
Setting:
1. To enable the function, select "Active" with
[OK].
2. To set the FLOW
, press [OK] to start the setting.
LIMIT
3. Select digit with
and
and adjust with
4. Press [OK] to save.
H
Q
25 %
max
Setting range
Q
Fig. 36 FLOW
LIMIT
The FLOW
function can be combined with the following
LIMIT
control modes:
Prop. press.
Const. press.
Const. temp.
Constant curve.
A flow-limiting function ensures that the flow never exceeds the
entered FLOW
value.
LIMIT
The setting range for FLOW
LIMIT
pump.
The factory setting of the FLOW
AUTO
factory setting meets the max. curve. See fig. 27.
ADAPT
30
or
and press
or
.
Q
90 %
max
Q
limit
is 25 to 90 % of the Q
of the
max
is the flow where the
LIMIT

13.5 Automatic Night Setback

Navigation
Home > Settings > Automatic Night Setback
Automatic Night Setback
To enable the function, select "Active" with
[OK].
Once Automatic Night Setback has been enabled, the pump
automatically changes between normal duty and night setback
(duty at low performance).
Changeover between normal duty and night setback depends on
the flow-pipe temperature.
The pump automatically changes over to night setback when the
built-in sensor registers a flow-pipe temperature drop of more
than +18 to +27 °F (-8 to -3 °C) within approx. two hours.
The temperature drop must be at least 0.18 °F/min (0.1 °C/min).
Changeover to normal duty takes place without a time lag when
the temperature has increased by approx. +18 °F (-8 °C).
Automatic Night Setback cannot be enabled
Note
Note
when the pump is in constant-curve mode.
or
and press