INSTALLATION AND SETUP
Electrical Installation
Maximum Motor Cable Length
Model
Motor Family
244 502 xxxx
244 504 xxxx
SubDrive
244 505 xxxx
Utility
244 507 xxxx
244 508 xxxx
244 509 xxxx
1
Based on a 5% voltage drop with 1000 ft limit.
Notes:
Drive input voltage and motor nameplate voltage must match.
The use of 600 V minimum rated motor cable is required.
Maximum allowable wire lengths are measured between the controller and motor, based on
AIM Manual requirements with 1000 ft limit. Larger wire and filtering are required if exceeding
the 1000 ft limit.
Flat-jacketed submersible motor cable is recommended. All splices in the motor cable must be
properly sealed with watertight shrink tubing. Use extreme caution to avoid damaging or
compromising the motor cable insulation during installation or service.
Conduit Locations and Sizing
Use appropriate strain relief or conduit connectors.
1. Incoming power supply—Hole = 0.88 in. (22.2 mm)
2. Power output to motor—Hole = 0.88 in (22.2 mm), Knockout = 1.11 in. (28.2 mm)
3. Control wiring (transducer/sensor) input—Hole = 0.5 in. (12.7 mm)
20
Motor
Horsepower
Voltage
115
1/3 (0.25 kW)
115
1/2 (0.37 kW)
230
1/2 (0.37 kW)
230
3/4 (0.55 kW)
230
1.0 (0.75 kW)
230
1.5 (1.1 kW)
AWG 600V Copper Wire Sizes, 75° C Insulation, and Motor Cable
Lengths (in feet)
14
12
10
100
160
250
100
160
250
400
650
1000
300
480
760
250
400
630
190
310
480
1
8
6
4
390
620
960
390
620
960
1000
990
770
1000