Risk of damage to VFD
Follow all wire routing and grounding instructions carefully. Inductive currents caused by paral-
lel wiring, or close proximity between high voltage and control wiring can cause unexpected
behaviors.
Do not run input power and motor wires in the same conduit.
Do not run motor wires from multiple VFDs in common conduit.
Do not run control wiring parallel with high voltage wiring.
Do not install a magnetic contactor or disconnect in the motor circuit.
Do not run VFD wiring parallel with house or out-building wiring.
Do not use aluminum wires for VFD connections.
Do not use with a Ground Fault Circuit Interrupter (GFCI) between breaker panel and motor.
All wiring must comply with the National Electrical Code and local codes.
Improper splicing or damage to motor cable insulation may expose the conductor(s) to
moisture and can produce motor cable failure.
Branch Circuit Protection
Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit
protection must be provided in accordance with the National Electrical Code and any additional
local codes, or the equivalent. Drive shall be protected by fuse or inverse-time circuit breaker only,
rated 300 V, and a maximum 300% of full load motor output current rating as noted in the table
below.
Fuse/Circuit Breaker and Wire Sizing
Model
Input
Motor HP
Voltage
115
1/2 (0.37 kW)
230
1/2 (0.37 kW)
SubDrive
230
3/4 (0.55 kW)
Utility
230
1.0 (0.75 kW)
230
1.5 (1.1 kW)
1
Based on a 3% voltage drop.
90 C Insulation only.
*
Note: SubDrive Utility minimum breaker amps may be lower than AIM Manual specifications
because of the soft-starting characteristic of the drive.
,
or malfunction can occur.
Fuse/Breaker
AWG Copper Wire Sizes, 75° C Insulation, and Panel to Drive Cable
Amps
14
*
15
40
15
130
15
130
*
20
70
25
Lengths (in feet)
12
10
8
6
60
100
155
245
205
340
525
835
150
250
390
620
*
185
285
450
110
140
215
340
INSTALLATION AND SETUP
Electrical Installation
1
4
3
2
1
390
485
635
805
1315
1635
2150
2720
975
1210
1595
2020
715
885
1165
1475
540
670
880
1115