Specifications
Supply Voltage Measurement
25-500V
Intrinsic accuracy ±2% ±2 digits
Supply Frequency Measurement
d.c., 16-460Hz
Intrinsic accuracy ±0,1% ±1 digit
Loop Resistance Measurement
(to EN 61557-3)
Line/Earth Loop
Displayed Range:
0,01Ω to 3,00kΩ
Nominal Supply:
230V, 50Hz
EN61557
Operating Range:
0,25Ω to 3,00kΩ
Intrinsic accuracy:
0,01Ω-9,99Ω
±4% ±0,03Ω
10,0Ω-89,9Ω
±5% ±0,5Ω
90Ω-899Ω
±5% ±5Ω
900Ω-3,00Ω
±5% ±20Ω
34
Line-Line (Phase/Phase) Loop Resistance
measurement (to EN 61557-3)
Displayed Range:
0,01Ω to 19,99Ω
Intrinsic accuracy:
±5% ±0,03Ω
Nominal Supply:
230V, 50Hz
EN61557
Operating Range:
0,25Ω to 19,99Ω
Prospective Fault Current
Prospective fault current = Nominal voltage
Measured Voltage
>150V
150V-300V
>300V
Prospective Fault Current is calculated from the
respective loop resistance. Ranges and accuracies are
therefore derived from the previous section.
Loop resistance
Nominal Voltage
110V
230V
400V