SERIAL COMMUNICATION INTERFACE
SERIAL COMMUNICATION INTERFACE
SERIAL COMMUNICATION INTERFACE
SERIAL COMMUNICATION INTERFACE
SERIAL COMMUNICATION INTERFACE
Type: RS-485 insulated.
Type
Type
Type
Type
Protocol type
Protocol type
Protocol type: MODBUS, JBUS, ERO polling/
Protocol type
Protocol type
selecting.
Baud rate
Baud rate
Baud rate: programmable from 600 to 19200
Baud rate
Baud rate
BAUD.
Byte format
Byte format
Byte format: 7 or 8 bit programmable.
Byte format
Byte format
Parity: even, odd or none programmable.
Parity
Parity
Parity
Parity
Stop bit
Stop bit
Stop bit
Stop bit
Stop bit : one.
Address
Address
Address :
Address
Address
- from 1 to 95 for ERO protocol
- from 1 to 255 for all the other protocols
Output voltage levels
Output voltage levels
Output voltage levels
Output voltage levels
Output voltage levels: according to EIA standard.
LFS-1-CC.P65
32
MAINTENANCE
MAINTENANCE
MAINTENANCE
MAINTENANCE
MAINTENANCE
1) REMOVE POWER FROM THE POWER SUPPLY
TERMINALS AND FROM RELAY OUTPUT
TERMINALS
2) Remove the instrument from case.
3) Using a vacuum cleaner or a compressed air jet
(max. 3 kg/cm
) remove all deposit of dust and
2
dirt which may be present on the louvers and on
the internal circuits trying to be careful for not
damage the electronic components.
4) To clean external plastic or rubber parts use
only a cloth moistened with:
- Ethyl Alcohol (pure or denatured) [C
- Isopropil Alcohol (pure or denatured)
[(CH
)
CHOH] or
3
2
- Water (H
O)
2
5) Verify that there are no loose terminals.
6) Before re-inserting the instrument in its case, be
sure that it is perfectly dry.
7) re-insert the instrument and turn it ON.
GB
GB
GB
GB
GB
32
13/07/2004, 14:40
H
OH] or
2
5