SEr3 = Baud rate for serial link
SEr3 = Baud rate for serial link
SEr3 = Baud rate for serial link
SEr3 = Baud rate for serial link
SEr3 = Baud rate for serial link
Not available when SEr1 = OFF
From 600 to 19200 baud.
NOTE
NOTE
NOTE
NOTE
NOTE: 19200 baud is shown on display as 19.20.
SEr4 = Byte format for serial link
SEr4 = Byte format for serial link
SEr4 = Byte format for serial link
SEr4 = Byte format for serial link
SEr4 = Byte format for serial link
Not available when SEr1 = OFF
7E = 7 bits + even parity (For ERO protocol only)
7O = 7 bits + odd parity (For ERO protocol only)
8E = 8 bits + even parity
8O = 8 bits + odd parity
8
= 8 bits no parity
P1 - Input type and standard range
P1 - Input type and standard range
P1 - Input type and standard range
P1 - Input type and standard range
P1 - Input type and standard range
0
= TC type
L
range
0 / +400.0°C
1
= TC type
L
range
0 /
2
= TC type
J
range -100.0 / +400.0 °C
3
= TC type
J
range
-100 / +1000 °C
4
= TC type
K
range -100.0 / +400.0 °C
5
= TC type
K
range
-100 / +1370 °C
6
= TC type
N
range
-100 / +1400 °C
7
= TC type
R
range
0 / +1760 °C
8
= TC type
S
range
0 / +1760 °C
9
= RTD type Pt 100 range -199.9 / +400.0 °C
10 = RTD type Pt 100 range
-200 /
11 = mV
Linear range
0 /
12 = mV
Linear range
12 /
13 = mA
Linear range
0 /
14 = mA
Linear range
4 /
15 = V
Linear range
0 /
16 = V
Linear range
1 /
17 = V
Linear range
0 /
18 = V
Linear range
2 /
19 = TC type
L
range
0 / +1650 °F
20 = TC type
J
range
-150 / +1830 °F
21 = TC type
K
range
-150 / +2500 °F
22 = TC type
N
range
-150 / +2550 °F
LFS-1-CC.P65
11
23 = TC type
R
range
24 = TC type
S
range
25 = RTD type Pt 100 range -199.9 / +400.0 °F
26 = RTD type Pt 100 range
27 = TC type
T
range -199.9 / +400.0 °C
28 = TC type
T
range
NOTE: selecting P1 = 0, 2, 4, 9, 25 or 27, the
NOTE
NOTE
NOTE
NOTE
instrument set automatically P36 = FLtr. For all
the remaining ranges it will set P36 = nOFL.
If a different selection is desired, P36 may be
modified.
P2 = Decimal point position
P2 = Decimal point position
P2 = Decimal point position
P2 = Decimal point position
P2 = Decimal point position
This parameter is available only when a linear input
is selected (P1 = 11, 12, 13, 14, 15, 16, 17 or 18).
----.
= No decimal figure.
---.-
+900 °C
= One decimal figure.
--.--
= Two decimal figures.
-.---
= Three decimal figures.
P3 = Initial scale value
P3 = Initial scale value
P3 = Initial scale value
P3 = Initial scale value
P3 = Initial scale value
For linear inputs it is programmable from -1999 to
4000.
For TC and RTD input it is programmable within
the input range.
+800 °C
60 mV
When this parameter is modified, rL parameter
will be re-aligned to it.
60 mV
20 mA
20 mA
P4 = Full scale value
P4 = Full scale value
P4 = Full scale value
5 V
P4 = Full scale value
P4 = Full scale value
5 V
For linear inputs it is programmable from -1999 to
4000.
10 V
10 V
For TC and RTD input it is programmable within
the input range.
When this parameter is modified, rH parameter
will be re-aligned to it.
GB
GB
GB
GB
GB
11
13/07/2004, 14:40
0 / +3200 °F
0 / +3200 °F
-330 / +1470 °F
-330 /
+750 °F