VOLTAGE OUTPUTS FOR SSR DRIVE
VOLTAGE OUTPUTS FOR SSR DRIVE
VOLTAGE OUTPUTS FOR SSR DRIVE
VOLTAGE OUTPUTS FOR SSR DRIVE
VOLTAGE OUTPUTS FOR SSR DRIVE
(For LFS-relay only)
(For LFS-relay only)
(For LFS-relay only)
(For LFS-relay only)
(For LFS-relay only)
+
6
+
OUT 1
_
_ _ _ _ _
7
SOLID STATE
RELAY
Fig. 11
SSR DRIVE OUTPUT WIRING
It is a time proportioning output.
Logic level 0
Logic level 0
Logic level 0
Logic level 0
Logic level 0: Vout < 0.5 V DC.
Logic level 1
Logic level 1
Logic level 1
Logic level 1
Logic level 1:
- 14 V + 20 % @ 20 mA
- 24 V + 20 % @ 1 mA.
Maximum current = 20 mA.
NOTE
NOTE
NOTE
NOTE
NOTE: This output is not isolated. A double or
reinforced isolation between instrument output
and power supply must be assured by the
external solid state relay.
LFS-1-CC.P65
7

SERIAL INTERFACE

SERIAL INTERFACE
SERIAL INTERFACE
SERIAL INTERFACE
SERIAL INTERFACE
RS-485 interface allows to connect up to 30
devices with one remote master unit.
I
A/A'
N
11
S
T
B/B'
R
12
U
M
COMMON
E
13
N
T
Fig. 12 - RS-485 WIRING
The cable length must not exceed 1.5 km at 9600
BAUD.
NOTE
NOTE
NOTE: 1) This is an RS485 isolated interface.
NOTE
NOTE
2)The following report describes the
signal sense of the voltage appearing
across the interconnection cable as
defined by EIA for RS-485.
a) The " A " terminal of the generator shall
be negative with respect to the " B "
terminal for a binary 1 (MARK or OFF)
state.
b) The " A " terminal of the generator shall
be positive with respect to the " B "
terminal for a binary 0 (SPACE or ON)
GB
GB
GB
GB
GB
7
13/07/2004, 14:40
A'/A
M
A
B'/B
S
T
E
R