CHAPTER 2
TECHNICAL FEATURES
NOTE
For the motor pump refer to the information contained in the specific manuals.
ATTENTION
Do not use the product in environments with acid, corrosive and/or inflammable gas.
ATTENTION
Do not use the motor pump with dangerous liquids.

2.1 FIELD LIMITATIONS

The CPS, configured in the same pressure group, can communicate and interact with a maximum of 8 electronic devices of the CPS3
Series. CPS complies with the Directive on Electromagnetic Compatibility EN 61800-3. In certain cases, some additional components
are required (like filters, etc...) to limit electromagnetic interferences. For more information please contact Customer Service. The
operation of this water pump with variable duty points may be more efficient and economic when controlled, for example, by the use of
a variable speed drive that matches the pump duty to the system. Information on benchmark efficiency is available at www.europump.
org/efficiencycharts
Environmental temperature:
+0°C a + 50°C
Temperature of pumped liquid:
refer to the specific motor pump
manual
Level of CPS protection: IP55
Level of system protection:
IP55 (if installed on motors with an IP55
or superior level)

2.2 INBOUND SIGNAL FEATURES

Pressure of transducer: (standard issue):
Pressure field: adapt to the maximum
head of the pump
Outbound signal: from 0 to 5 Volt
CHAPTER 3
INSTALLATION
ATTENTION
The installation operations must be performed by expert, qualified personnel.
ATTENTION
Use specific guards and equipment as per safety standards.
ATTENTION
Fully comply with safety and accident prevention standards in force.
Carefully read the use and maintenance manual for the pump.
Maximum operational pressure:
refer to the specific motor pump
manual
Voltage of inverter:
3x380-500 Vac
Voltage of outlet inverter:
3x380-500 Vac
Inbound frequency: 50/60 Hz
Connection: ¼ male
Maximum power at outlet:
5,5 kW
7,5 kW
Maximum nominal outbound current:
11,5 A
16 A
Wave shape: sinusoidal
Inbound filter:
complies with EMC directive
Electrical connector: removable,
provided with 2 m of cable
EN
25