Relay Output; Application Examples - Afriso EURO-INDEX ÖWWG 3 Notice Technique

Appareil d'avertissement huile-eau
Masquer les pouces Voir aussi pour ÖWWG 3:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3.4

Relay output

3.5

Application examples

ÖWWG 3
ÖWWG 3 is equipped with an output relay to transmit the alarm sig-
nal to additional equipment.
ÖWWG 3 can be operated with or without additional equipment, for
example:
Visual and audible alarm units
Remote alarm equipment
Building control systems
Other
Fig. 3: Waste water pump control with automatic oil safety facility
The operation of automatic drainage pumps in collecting areas of oil
storage rooms implies the danger of oil reaching the sewage system
in case of a tank leak. The combination of ÖWWG 3 and ELT 8 with
probes selected for this purpose prevents oil damage. The waste wa-
ter pump is controlled by ELT 8 and a 3-rod probe and pumps the
water from the soakaway. The pump is switched on when the water
has reached the maximum level and switched off when it has fallen
to the minimum level. Since ELT 8 operates on the basis of the con-
ductivity principle, any oil that may result from a leak and floats on
the water is not detected by ELT 8 since oil is not conductive. The
PTC thermistor probe of ÖWWG 3 is submerged in the oil on the wa-
ter. ÖWWG 3 triggers visual and audible alarms and keeps the
waste water pump from being switched on.
– English –
Product description
1
Mains voltage
2
Control unit
3
Control line
4
Waste water pump
5
PTC thermistor
probe
6
Maximum level
7
Minimum level
8
Residual water
11