Safety

2.1

Intended use

2.2

Predictable incorrect application

ÖWWG 3
The ÖWWG 3 oil/ water alarm unit may only be used to signal accu-
mulations of liquids and only to monitor:
Collection facilities under storage tanks, burners or motors
Tanks with collection facilities which are not visible
Collection facilities for devices consuming oil or water
Rooms for early indication of water leaks
Manholes, pipe and cable ducts (frost-free)
Pump and control stations which are subject to leaks, backflow
or flooding
Storage and transport of liquids
The ÖWWG 3 oil/water alarm unit may only be used for the following
liquids at atmospheric pressure and up to a maximum of 45 °C:
Water,
Fuel oil EL, L or M,
Diesel fuel (DIN EN 590) and low-viscosity with flash point
> 55 °C,
Unused and used motor oils (for example, SAE 15W-40), gear-
box oils and hydraulic oils, transformer oils, vegetable oils
Antifreeze agents,
Oil/water mixtures, emulsions,
ÖWWG 3 is suitable for liquids (flash point > 55 °C) with equivalent
heat conductivity if these liquids are compatible with the following
wetted parts:
Wired PTC thermistor (glass + silver wire)
Plastic: PA6 (Furkamid B SK 1)
Cable: Ölflex 100, resistant to acids, lye and oils
Leak detection system class III as per DIN EN 13160-1 and
DIN EN 13160-4 as liquid sensor system in leak or interstitial spaces,
as safety device as per worksheet DWA-A 791 and leak detection
system as per worksheet DWA-A 779.
Any use other than the application explicitly permitted in these oper-
ating instructions is not permitted and causes hazards.
The ÖWWG 3 oil/water alarm unit must never be used in the follow-
ing cases: