Output Current Limitation - Cristec DC-DC YPOWER Série Manuel Utilisateur

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3.3.10 CAN Bus
The regulator offers two receptacles matching with connectors Molex Microfit 3.0, 6 circuits (reference 43025-0600).
Documentation n° 1336205REG_CAN (hardware and software specification) is available upon request.
3.3.11 Remote display
The battery charger supports the remote tactile colour display UNI-DISPLAY-R.
3.3.12 Remote control
This option G-ON/OFF-R allows you to shut down the remote charger from a two-wire cable.
The converter is stopped if both wires are short-circuited
3.3.13 Factory setting
The charger's factory settings are: sealed Lead, BOOT ON
This setting is a compromise for satisfactory recharging of different technologies of battery:
-
Opened classic lead
-
Sealed, Gel or AGM
-
Spiral sealed
-
Lithium Iron Phosphate ( LiFePO4 ) with BMS
To define the charge in function of your battery, please refer to the chart, paragraph : 3.3.2.
For special batteries, call in a professional installer, who will make the specific settings in accordance with the battery
manufacturer's specifications and according to the specifics of the installation.
CRISTEC is not liable for any damage caused to the batteries or for inefficient recharging.

3.3.14 Output current limitation

In order to protect the output power, the YPOWER charger has an output current limitation according to the output
voltage.
Output Current
10% of Nominal
Output current
42% of Nominal
output voltage
Iout = Nominal current
83% of Nominal output
voltage
Output Voltage
37