Output Current
Iout = 0A
3.3.8 Programming field 7 : output current limitation
3.3.9 Thermal compensation
STP-UNI-2.8 and STP-UNI-5.0 temperature probes enable the compensation of Absorption voltage and Floating
Voltage depending on the ambient temperature of the battery room.
The coefficient used is -18mV/°C for 12V model and -36mV/°C for 24V models.
Temperature is not compensated when Wintering (or standby sealed bat), Stabilized DC power supply and Lithium Iron
Phosphate (LiFePO4) with BMS settings are selected.
0.5V ( for 12V input )
1.0V ( for 24V input )
Input start-up
voltage
Output current
Setting
limitation
1
10%
2
20%
3
30%
4
40%
5
50%
6
60%
7
70%
8
80%
9
90%
10
100%
Iout = Nominal current
Input Voltage
36