3.3.15 Charging curve

When BOOST mode is selected
With this setting the YPOWER charger delivers a 5-step charge curve IUoU return to automatic BOOST : BOOST,
ABSORPTION, FLOATING + REFRESH, REBOOST.
V BOOST :
BOOST voltage (see table above)
V FLOAT :
FLOATING voltage (see table above : voltage with no BOOST)
T BOOST :
BOOST maximum duration (see table above – paragraph 3.3.2)
T ABS :
ABSORPTION maximum duration (see table above – paragraph 3.3.2 )
BOOST phase :
Starts up automatically when the charger is turned on if the battery is flat. The current is then at maximum output.
ABSORPTION phase :
Begins when the voltage has reached the maximum BOOST level. The current level starts falling.
These two phases combined last a maximum of TBOOST+TABS (depending on setting). If the current falls below 20% of
rated current, the FLOATING phase automatically kicks in. Duration and current intensity depend on how charged the
battery is.
FLOATING phase :
Starts after TBOOST or if output current has reached 20% of the charger's rated current. The voltage switches to the
FLOATING value and the rated current continues to drop.