Acknowledging Errors - salmson LRE Notice De Montage Et De Mise En Service

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 1
English
Classification No.
E072 Power section/fre-
E075 Charging relay defec-
E076 Internal transformer
E077 24 V operating voltage
E096 Infobyte not set
E097 Flexpump data record
E098 Flexpump data record
Impermissi-
E099 Pump type
ble combina-
torics
11.3

Acknowledging errors

General
6.0.0.0
E000
6.0.0.0
10
1/1
Fig. 39: Navigation in case of error
89
Error
quency converter
tive
defective
for sensor defective
missing
invalid
E000
5.0.0.0
S
Cause
Remedy
Internal electronics error
Contact customer service
Internal electronics error
Contact customer service
Internal electronics error
Contact customer service
Sensor defective or con-
Check differential pressure
nected incorrectly
sensor connection
Internal electronics error
Contact customer service
Internal electronics error
Contact customer service
Internal electronics error
Contact customer service
Different pump types
Contact customer service
have been intercon-
nected
In the event of an error, the error page is displayed instead of the sta-
tus page.
In this case, the following procedure can generally be used for naviga-
tion (Fig. 39):
• To change to menu mode, press the white button.
Menu number <6.0.0.0> flashes on the display.
By turning the white button, it is possible to navigate in the menu as
usual.
• Press the white button.
Menu number <6.0.0.0> appears steady on the display.
On the units display, the current incidence (x) as well as the maximum
incidence of the error (y) are displayed in the format "x/y".
Until the error can be acknowledged, pressing the white button again
will cause a return to menu mode.
NOTE:
A 30-second time-out causes the display to revert to the status page
or error page.
NOTE:
Every error number has its own error meter, which counts the inci-
dence of the error within the last 24 hours and is reset after manual
acknowledgement, 24-hour continuous "mains On" or a new "mains
On".
Error type
HV
AC
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
Pompes Salmson 04/2011

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Jre

Table des Matières