5.2. Programming (cont.)
5.2.7. Inputs / Outputs Menu (cont.)
Inputs
Variable
Description
d'entrée
Ft1
Fault input 1. The fault led is blinking as soon as the input is active and Ft1 is displayed on LCD.
Reset when the input is de-activated.
Ft2
Fault input 2. The fault led is blinking as soon as the input is active and Ft2 is displayed on LCD.
Reset when the input is de-activated.
Ft3
Fault input 3. The fault led is blinking as soon as the input is active and Ft3 is displayed on LCD.
The transfer switch is immediately driven in 0 position (only in contactor mode).
Keypad action (Validation) necessary to Reset the fault.
Ft4
Fault input 4. The fault led is blinking as soon as the input is active and Ft4 is displayed on LCD.
The transfer switch is immediately driven in 0 position (only in contactor mode).
Keypad action (Validation) necessary to Reset the fault.
Pri
Priority network selection.
(1)
Network
Mtf
Remote manuel re-transfer. Feature identical to manual retransfer on keypad.
Re-transfer from backup network to priority network is allowed from input activation (1 s front).
The Mtf variable in the setup menu must be selected (Yes) to allow input recognition.
S2A
Information source
S2A is selected).
Man
Information transfer system in manual mode.
All automatic commands (+ test on load) are inhibited as soon as the input is activated.
CtS
Remote transfer control. Possible to initiate transfer from priority source to backup source before 2AT ends.
If 2AT is set to its maximum value (60s), the transfer is initiated as soon as the input is activated (1 s front).
tol
Remote test on load. Started from input activation.
Re-transfer is blocked until input de-activation.
tfl
Remote test off load.
Started from input activation (remote genset start / stop).
EJP
2 inputs are automatically affected to EJP.
• Input 1 for EJP advice, to start generator.
• Input 2 to transfer on emergency source.
Retransfer is activated when input 2 disappears.
(1) This information is the only considered in case of option configuration.
Programming variable Pri is then inhibited.
5.2.7-1
EJP cycle
52
ATyS C20 / C30 - Ref. : 532 214 F
1 2
1
has priority when input is not activated. Network
2
available (Genset) used instead of voltage / frequency measurement (inhibited when
EJP advice (input 1)
EJP transfer (input 2)
Start generator
2AT
Source 1
Source 2
5. OPERATION
2
has priority if input is active.
2CT
1DT
2DT