4.1. Control circuits (cont.)
4.1.4. 400 vac (P-P) application with neutral conductor
circuit breaker type technology
Electrical interlocking not integrated
• Configure the type of control logic in breaker (see Programming chapter)
• Automatic Power supply 203-205 or 104-106 (see Power supply chapter).
L1
L2
1
L3
N
ONLy ON ATyS C30
* Only on DC versions.
Maximum control cables leng = 10 m. In case of longer distance, insert control relays.
Remote interfaces maximum connection cable (RJ45) = 3 m.
This drawing is not including the electrical interlock.
It might be necessary for some breakers not to set up 1DT and 2DT timers to 0. (Refer to programming).
42
ATyS C20 / C30 - Ref. : 532 214 F
F1
CLOSING
Breaker 1
GE
13 14 23 24 33 34 43 44 53
Cable
RJ45 8/8
N
ATyS D10 or D20
103
remote interface
LOAD
OPENING
Breaker 1
Breaker 2
Breaker 2
54
301 302 303 304 305 306
L3
L2
L1
104
105
106
4. CONNECTIONS
L1
L2
L3
N
F2
F1, F2
Fuse protection
I1 I2
DC-* DC+*
L1
L3
203
205
2
230 Vac 5 A