10.7 Exit delay
This menu item allows the exit delay time to be programmed in the alarm control centre. This time period is
observed for the correspondingly programmed loops once the alarm is armed.
Memory location
(press the displayed
digits on the control
panel)
30
Code =
acoustic display for exit delay countdown
0 =
acoustic signal is deactivated
1 =
acoustic signal is activated (factory setting)
Time =
The exit delay period can be between 2 and 999 seconds long.
The factory setting is 60 seconds long.
10.8 First entry delay
This menu item allows the first entry delay time to be programmed in the alarm control centre. This time
period is observed for the correspondingly programmed loops once there is a resistance change (see
configuration of alarm loops code 2).
Memory location
(press the displayed
digits on the control
panel)
31
Code =
acoustic display for first entry delay countdown
0 =
acoustic signal is deactivated
1 =
acoustic signal is activated (factory setting)
Time =
The first entry delay period can be between 2 and 999 seconds long.
The factory setting is 30 seconds long.
10.9 Second entry delay
Here you can set the second entry delay period (see configuration of alarm loop code 2)
Memory location
(press the displayed
digits on the control
panel)
32
114
Code
(enter the desired code on
the control panel)
0 or 1
Code
(enter the desired code on
the control panel)
0 or 1
Code
(enter the desired code on
the control panel)
0 or 1
Time
(enter the desired time in
seconds using the control
panel)
2 to 999
Time
(enter the desired time in
seconds using the control
panel)
2 to 999
Time
(enter the desired time in
seconds using the control
panel)
2 to 999
Confirmation
(press the displayed
button on the control
panel)
#
Confirmation
(press the displayed
button on the control
panel)
#
Confirmation
(press the displayed
button on the control
panel)
#