Fig. 69: Menu 2.05
Fig. 70: Menu 3.02
Fig. 71: Menu 3.01
8.5.1
Adjust motor current monitoring
Installation and operating instructions Wilo-Control EC-L
Commissioning
Menu no.
Description
Value range
Factory setting
Menu 3: Enable pumps
To operate the system, the operating mode must be set for each pump and the pumps
enabled:
▪ At the factory, every pump is set to the "auto" operating mode.
▪ Automatic mode starts after the pumps have been enabled in menu 3.01.
NOTICE! Required settings for the initial configuration.
During the initial configuration, a direction of rotation check must be performed on the
pumps and the motor current monitoring set exactly. The following settings must be
made to perform the initial configuration:
▪ Switch off the pumps: Set to "off", menu 3.02 to 3.04.
▪ Enable pumps: Menu 3.01 set to "on".
Menu no.
Description
Value range
Factory setting
Explanation
Menu no.
Description
Value range
Factory setting
Explanation
DANGER
Risk of fatal injury due to electrical current!
Only operate the switchgear when closed. There is a risk of fatal injury from open
switchgear! Electrical work on the internal components must be carried out by a
qualified electrician.
Show the current value of the motor current monitoring
1. Press the operating button for 3 s.
⇒ Menu 1.00 appears.
2. Turn the operating button until menu 4 appears.
3. Press the operating button.
⇒ Menu 4.01 appears.
4. Turn the operating button until menu 4.25 to 4.27 appears.
2.05
Number of stop bits
1; 2
1
3.02 ... 3.04
Operating mode pump 1 ... Pump 3
off, Hand, Auto
Auto
off = pump switched off
Hand = manual operation pump, as long as the button is
pressed.
Auto = level-control dependent automatic operation of the
pump
NOTICE! For the initial configuration, change the value to
"off"!
3.01
Enable pumps
on, off
off
off = pumps are locked and cannot be started. NO-
TICE! Manual operation or forced switch-on are also not
possible!
on = pumps are switched on/off, depending on the operat-
ing mode set
en
87