7.7
Factory settings
8
Commissioning
8.1
Operator responsibilities
8.2
Commissioning in explosive atmo-
spheres
Installation and operating instructions Wilo-Control EC-L
Commissioning
Reset the current error message
NOTICE! Menu point is only shown when an error is present!
Manual operation pump 1
If the operating button is pressed, pump 1 runs.
If the operating button is released, the pump switches off. The last
set operating mode is active again.
Manual operation pump 2
If the operating button is pressed, pump 2 runs.
If the operating button is released, the pump switches off. The last
set operating mode is active again.
Manual operation pump 3
If the operating button is pressed, pump 3 runs.
If the operating button is released, the pump switches off. The last
set operating mode is active again.
Pump 1 switch off.
Corresponds to the "off" value in menu 3.02.
Pump 2 switch off.
Corresponds to the "off" value in menu 3.03.
Pump 3 switch off.
Corresponds to the "off" value in menu 3.04.
Automatic mode, pump 1
Corresponds to the "Auto" value in menu 3.02.
Automatic mode, pump 2
Corresponds to the "Auto" value in menu 3.03.
Automatic mode, pump 3
Corresponds to the "Auto" value in menu 3.04.
To reset the switchgear to the factory settings, contact customer service.
▪ Provide installation and operating instructions at the switchgear or at a place specially
reserved for it.
▪ Make the installation and operating instructions available in a language the personnel
can understand.
▪ Make sure that the installation and operating instructions are read and understood by
all personnel.
▪ The installation site of the switchgear is overflow-proof.
▪ The switchgear must be properly fused and earthed.
▪ The signal transmitter must be installed and set in accordance with the system docu-
mentation.
▪ Observe the minimum water submersion of the connected pumps.
▪ Safety devices (incl. emergency off) of the entire system are switched on and checked
for trouble-free operation.
▪ The switchgear is suitable for use under the specified operating conditions.
The switchgear may not be put into operation in potentially explosive atmospheres!
en
77