MANUAL MODE -OK-
▲ ▼ Manual flushing -OK-
Pipes 1 - 4
-OK-
Enter running time in secs 0000
Each flashing digit must be selected with the arrow button and
confirmed with -OK-. If the time has been fully set, confirm this
with -OK- or return with -ESC-.
If you do not wish to enter any further pipes, press -ESC- again
and you are now back in the "Handmodus" menu.
▲ ▼ Manual units -OK-
Only for customer service.
SYSTEM SETTINGS -OK-
You can now select various sub-menus with ▲ ▼ . Once you
press -OK-, you will be asked to enter a password.
The factory default setting is "0000". Each of the four digits
must be confirmed with -OK-. This means that in the case of
the factory default setting, for example, you will have to press
-OK- four times. You are now in the relevant sub-menu.
▲ ▼ Set date -OK-
Each flashing digit must be selected with the arrow button and
confirmed with -OK-. The day of the week is set automatically.
Once the full date has been set, a "Datum ok?" query follows.
Confirm with -OK- or return with -ESC-.
▲ ▼ Set clock -OK-
Each flashing digit must be selected with the arrow button and
confirmed with -OK-. Once the full time has been set, a "Uhrzeit
OK?" query follows. Confirm with -OK- or return with -ESC-.
▲ ▼ Sommer/Wintertime -OK-
The automatic changeover from summer to winter time is
switched on and off here.
▲ ▼ Change password -OK-
All four digits must be confirmed with -OK-. This is followed up
with a final prompt for confirmation. The new password can be
noted in this instruction manual.
_ _ _ _ • _ _ _ _ • _ _ _ _ • _ _ _ _ • _ _ _ _ •
▲ ▼ Service menu -OK-
For the manufacturer only
▲ ▼ Service interval -OK-
The service interval counter can be reset here.
▲ ▼ Reset to default settings -OK-
You can carry out a reset here. The unit will be reset to the fac-
tory default settings and a restart will be carried out.
-OK-
▲ ▼ Alarm buzzer -OK-
The alarm buzzer can be switched on and off here.
▲ ▼ Button beep -OK-
The beep which sounds when a button is pressed can be tur-
ned on or off here.
▲ ▼ Language -OK-
The arrow buttons can be used to switch to English, French,
Dutch, Swedish or Polish. Pressing -OK- confirms the selec-
tion.
▲ ▼ Ventilator -OK-
SH: If the ambient temperature is too high, one ventila-
tor switches on automatically. With the SH3, two ventilators
switch on.
The factory default setting is 35°C. It can be changed here to
any value between 20 and 39°C.
▲ ▼ Oil level PPCS -OK-
Selection: normally closed or normally open contact.
▲ ▼ Station ID -OK-
This menu item displays the identifier of the station.
▲ ▼ Cleaning threshold -OK-
If the PPCS is blocked by the pump during cleaning, this de-
fines whether cleaning should continue after blocking has
been released.
0% = Stop cleaning
75% = Stop cleaning if 75% of cleaning time completed
100% = Keep cleaning

POSSIBLE ERROR MESSAGES

PSV overpress. The pump sump ventilation has shut down for
safety reasons because the pressure was more than 6 bar.
PPCS overpress. The pressure pipe ventilation has shut down
for safety reasons because the pressure was more than 6 bar.
Check whether the shut-off devices for the pressure pipe in
the chamber and for the flushing device are open.
Furthermore, there may be a blockage in the pressure pipe. In
this case, clear the obstruction.
SafStat40. The ambient temperature exceeded 40°C, and the
unit was shut down for safety reasons.
Frost. The ambient temperature has dropped below 0 °C.
Power failure. The power supply has failed.
M-I. Motor protection. The compressor motor protection
switch has tripped.
Date/Time. The date and time must be re-entered.
Communication. No response received from a module.
ENGLISH