Boost in OFF position
With this setting, the CPS2 charger produces a single-stage UI type load curve. It generates a constant voltage,
supplying the current required by the battery(ies). Recharging time depends on the state of the battery, being
longer than when the boost is in the ON position.
3.2.6 Indicators
INDICATOR
Green "ON"
Yellow "Boost/Absorption"
Yellow "Floating"
These indicators are visible from the front of the appliance through the light guides, thereby allowing operation
of the appliance to be monitored.
U out
charger
U floating
0
I out
charger
I nom
0
On
Off
On
Flashing
Off
On
Off
CPS2DEA.DOC
t
t
STATE
or
or
or
or
MEANING
- Charger is ON
- No or poor quality AC current
- Input fuse blown
- Internal charger malfunction
- SW1 Switch:
Boost in OFF position
- SW1 switch:
Boost
in
ON
position
Boost/Absorption phase completed
- SW1 Switch:
Boost in ON position and charger in
the Boost/Absorption phase
- Internal charger malfunction
- Output fuse blown
Charger current < 15% of rated
current (Floating phase)
> 15% rated
Charger current
current
30
and