Cps2 12V/40A, 24V/20A, 12V/60A, 24V/30A, 48V/15A - Cristec CPS2 12V/16A Manuel D'utilisation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 1

2.2 CPS2 12V/40A, 24V/20A, 12V/60A, 24V/30A, 48V/15A

Models
Input
Voltage
Frequency
Current intensity 230/115VAC
Power factor
Efficiency
Input fuses F1/F2
Output
Number of outputs
Overall
rated
current
7%)/Rated power
Load curve
Type of batteries
Regulated and filtered output
voltage
Regulation tolerance before
distributor and fuses
Peak-to-peak ripple and noise
Automotive output fuses
mounted in parallel in the BAT
pole -
Environment
Operating temperature
Cooling
Relative humidity
Case
Material
Paintwork
Dimensions excluding cable
gland (length, height,
depth)/Weight
Fixing centre distances
Wall screw
Protection factor
Board protection
Standards
CE/CEM markings
CE/safety markings
Electrical protection
CPS2/12-40
CPS2/24-20
From 85 to 265VAC, single-phase
De 47 to 63Hz
3.2A/6.6A
0.9 in rated conditions
> 80% in rated conditions
2 x 10A/250V – 6.3x 32
3 separate outputs BAT D, BAT 1 and BAT 2 (integrated distributor). Each output can
be used on its won and supply the entire current.
(+/-
40A/570W
Type of charge selected using internal switch IU or IUoU (Boost, Absorption, Floating
– factory setting).
See switch settings table
See switch settings table. Chargers can operate on DC supply.
< 2%
< 250mV
2 x 20A/32V
(F3/F4)
-10°C to +45°C ; +45°C to +60°C with 4% de-rating of rated Power/°C
Draft fan controlled by internal temperature probe 60°C +/-5°C
Up to 70% (95% with no condensation)
Case comprises 3 parts: aluminium frame and steel flap and hood
Mat black, yellow, and grey epoxy coating
288 x 209 x 115mm / 5Kg
266.5 x 110mm
4 M5 round screws
IP21
Protected with water-repellent varnish (marine environment)
NF EN6100-6-1, NF EN6100-6-2, NF EN6100-6-3, NF 6100-6-4
NF EN60950, NF EN603635-2-29
-Against leaking input surges by rupture of VDR (voltage-dependent resistor)
-Against output polarity reversals by rupture of fuses, except 48-Volt models
-Against output short-circuits and surges
-Against abnormal overheating by cutting off the charger (internal temperature probe
90°C)
-Against output surges
CPS2DEA.DOC
CPS2/12-60
3,1A/6,4A
4.6A/9.4A
20A/570W
60A/855W
< 500mV
< 250mV
1 x 20A/32V
3 x 20A/32V
(F3)
(F3/F4/F5)
CPS2/24-30
CPS2/48-15
4.4A/9A
2 x 15A/250V – 6.3x 32
30A/855W
< 500mV
2 x 15A/32V
(F3/F4)
25
4.3A/8.8A
15A/855W
< 1000mV
Sans

Publicité

Table des Matières
loading