Tightening Torques For Diaphragms - Burkert 3232 Manuel D'utilisation

Masquer les pouces Voir aussi pour 3232:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Type 3232, 3233, 3233 K, 3234,
3235, 3239
Procedure:
Cross-loosen fastening screws and remove actuator with dia-
phragm from the housing.
Weld or glue housing in the pipeline.
After welding or gluing in the housing, smooth the housing surface
(if required) by grinding.
Clean the housing carefully.
Place actuator on the housing.
Lightly cross-tighten the fastening screws until the diaphragm is
between the housing and actuator.
Do not tighten screws yet.
Activate the diaphragm valve twice to position the diaphragm
correctly.
Tighten the fastening screws up to the permitted tightening
torque (see tables in chapter „8.3.2. Tightening torques for
diaphragms").
Installation
8.3.2. Tightening torques for diaphragms
Orifice
Diaphragm
(Diaphragm size)
EPDM / FKM
DN [mm]
8
15
20
25
32
40
50
Tab. 8:
Tightening torques for diaphragms. Actuator PPS or
stainless steel
Orifice
Diaphragm
(Diaphragm size)
EPDM / FKM
DN [mm]
65
80
100
Tab. 9:
Tightening torques for diaphragms. Actuator stainless steel
english
Actuator PPS or stainless steel
Diaphragm
PTFE/advanced
PTFE/laminated
advanced PTFE
2
2,5
3,5
4
4
4,5
5
6
6
8
8
10
12
15
Actuator stainless steel
Diaphragm
PTFE/advanced
PTFE/laminated
advanced PTFE
20
30
30
40
40
50
17

Publicité

Table des Matières
loading

Table des Matières