Analogue outputs

type
0 to 10 Vdc optically-isolated
maximum number
4, 4, 6, on the SMALL, MEDIUM and EXTRALARGE N.O./N.C., LARGE boards respectively
power supply
external 24 Vac/Vdc
resolution
8 bit
maximum load
1 k (10 mA)
precision
± 2 % of end scale on outputs: Y1, Y2, Y3 and Y4
-2%/+5% of end scale on: Y5 and Y6

Digital outputs

type
relay
maximum number
8: SMALL; 13: MEDIUM; 18: LARGE; 27: EXTRALARGE N.C.; 29: EXTRALARGE N.O.
For the requirements refer to Figs. 3 to 5 (reference NO*, NC* and C*). Note the presence of outputs with changeover contacts kept separately (that is,
without the poles shared between different outputs). Groups from 2 to 5 outputs have 2 "common" poles for easy assembly. Make sure that the current
running through the common terminals does not exceed the rated current of each individual terminal, that is 8A.
Insulation distance
the outputs can be divided into groups. There is double insulation between groups (between cells in the table).
Note: the relays in the same group must have the same power supply (24 or 230 Vac).
Makeup of the groups
version
SMALL
Type of relay
MEDIUM
Type of relay
LARGE
Type of relay
EXTRALARGE N.O.
Type of relay
EXTRALARGE N.C.
Type of relay
Note: the relays in the individual cells of the table have basic insulation between them, while between groups (cell-cell)
there is double insulation.
Changeover contacts
1: SMALL (relè 8); 3: MEDIUM e EXTRALARGE N.O./N.C. (relè 8, 12 e 13); 5: LARGE (relè 8, 12, 13, 14 e 15)
Switchable power
warning: the relay outputs have different characteristics according to the model of pCO
relay
type A
relay
type B
relay
type C
SSR outputs
1: SMALL (output 7); 2: MEDIUM (outputs 7 & 12); 3 or 4: LARGE (outputs 7, 12 & 14 or 7, 12, 14 &15)
(optional on the models
Operating voltage: 24 Vac/Vdc; Maximum load current = 0,5A; Maximum pulse load current = 1,2A.
where featured)
If the load requires a higher current, use an external SSR.
To power external loads, use the same power supply as the pCO (connected to terminals G/G0); as
specifi ed by Carel, this must always be dedicated and not in common with the power supply to other devices on the electrical
panel (such as contactors, coils, etc.).
Make sure that the load connection cables are as short as possible and away from power cables. For the connection diagrams
see the pCOSistema manual +0300009IT.
Relation between AWG and wire cross-section
AWG
Cross-section (mm
20
0.5
15
1.5
14
2.5
pLAN network/user terminal connection
type
transmission speed
terminal connector
pLAN network/graphic terminal/aria terminal connector
+050003290 - 1.6 - 03.08.2011
relays with same insulation
1...7
A type
1...7
A type
1...7
A type
1...7
A type
1...7
A type
type of relay:
SPDT, 2000 VA, 250 Vac, 8 A resistive
pCO
3
approval: UL873: 2.5 A resistive, 2 A FLA, 12 A LRA, 250 Vac, C300 pilot duty (30000 cycles)
EN 60730-1: 2 A resistive, 2 A inductive, cos= 0.6, 2(2) A (100000 cycles)
type of relay:
SPDT, 1250 VA, 250 Vac, 5 A resistive
3
pCO
approval: UL873: 1 A resistive, 1 A FLA, 6 A LRA, 250 Vac, D300 pilot duty (30000 cycles)
EN 60730-1: 1 A resistive, 1 A inductive, cos= 0.6, 1(1) A (100000 cycles)
type of relay:
SPDT, 1250 VA, 250 Vac, 5 A resistive
pCO
3
approval: UL873: 1 A resistive, 1 A FLA, 6 A LRA, 250 Vac, D300 pilot duty (30000 cycles)
EN 60730-1: 1 A resistive, 1 A inductive, cos= 0.6, 1(1) A (100000 cycles)
2
)
Current
2
6
8
RS485 half-duplex asynchronous
62.5 Kbps or 115.2 Kbps, selectable via software
6 pin telephone (J10)
3 pin plug-in connector (J11)
8
-
-
A type
8
9...13
-
A type
A type
8
9...13
14...18
A type
A type
A type
8
9...13
14...16
A type
A type
B type
8
9...13
14...16
A type
A type
C type
13
-
-
-
17...20
21...24
25...29
B type
B type
B type
17...20
21...24
25...27
C type
C type
C type
3