TECHNICAL SPECIFICATIONS

Mechanical characteristics

dimensions
SMALL version fi tted on 13 DIN rail modules, 110 x 227.5 x 60 mm
MEDIUM, LARGE and EXTRALARGE version fi tted on 18 DIN rail modules, 110 x 315 x 60 mm
installation
DIN rail
Plastic case
• fi tted on DIN rail according to DIN 43880 and CEI EN 50022 standards;
• material: technopolymer;
• fl ame retardancy: V0 (UL94) and 960°C (IEC 695);
• ball pressure test: 125°C;
• resistance to creeping current: 250 V;
• colour: grey RAL7035;
Adjust the contrast
In graphic-diaply version is possible to adjust the costrast. To do this:
1. press the Enter and Esc buttons together;
2. holding the two buttons, use UP or Down to adjust the contrast as required (increase or decrease respectively).
Electrical specifi cations
power supply (controller with
terminal connected)
terminal block
CPU
memory (FLASH MEMORY)
data memory (static RAM)
parameter data memory
working cycle duration (applications
of average complexity)
clock with battery

Digital inputs

type
maximum number
classifi cation of the measuring
circuits (CEI EN 61010-1)
WARNINGS: - 230 Vac 50/60 Hz (10/-15%);
- the two 230/24 Vac inputs present on J8 and J12 have the same common pole and consequently will be both 24 Vac/Vdc or both 230 Vac.
Basic insulation between the two inputs;
- for DC inputs, connect the negative pole to the common terminal.
Note: separate as much as possible the probe and digital input signal cables from the cables carrying the inductive loads and the power cables, to avoid
possible electromagnetic disturbance.

Analogue inputs

analogue conversion
type
maximum number
time constant for each input
precision
classifi cation of the measuring
circuits (CEI EN 61010-1)
WARNING: the 21 Vdc available at the +Vdc terminal (J2) can be used to power any active probes, the maximum current is 150 mA, thermally protected against
short-circuits. To supply the ratiometric 0 to 5 V probes, use the +5VREF (Imax: 60 mA) present at terminal J24.
+050003290 - 1.6 - 03.08.2011
28 TO 36 Vdc +10/-20% and 24 Vac +10/-15% 50 to 60 HZ
maximum power input P= 15 W (24 Vdc power supply), P= 40 VA (24 Vac)
with plug-in male/female connectors, max voltage 250 Vac;
cable cross-section: min. 0.5 mm
H8S2320, 16 bit, 24 MHz
2+2 MB; in the extended versions further memory of 32 MB or higher
512 kB at 16 bit (296 kB BIOS; 216 application sw)
13 kB at 16 bit (max. limit: 100,000 writes per memory location) and a further 32 kB E
0.2 s (typical)
standard
optically-isolated
8, 14, 18, respectively on the SMALL, MEDIUM and EXTRALARGE N.O and N.C., LARGE boards, according to the
combinations shown below:
optoinsulated input no. to 24 Vac
SMALL
MEDIUM/EXTRALARGE
LARGE
Category I (J5, J7, J20) 24 Vac/Vdc
Category III (J8, J19) 230 Vac
10 bit A/D converter in the CPU
universal:
(inputs B1, B2, B3, B6, B7, B8) CAREL NTC temperature sensor (-50T90°C; R/T 10 k at 25°C), HT NTC
0T150°C, voltage: 0 to 1 Vdc, 0 to 5 V ratiometric or 0 to 10 Vdc, current: 0 to 20 mA or 4 to 20 mA, selectable via
software. Input resistance in 0 to 20 mA= 100
passive:
(inputs B4, B5, B9, B10) CAREL NTC temp. sensor (see universal type),
PT1000 (-100T200°C; R/T 1000  at 0°C) or voltage-free digital input (5 mA), selectable via software;
5, 8, 10, on the SMALL, MEDIUM and EXTRALARGE N.O., LARGE and EXTRALARGE N.C. boards respectively
0.5 s
± 0.3 % of full scale
Category I
2
2
- max 2.5 mm
50/60 Hz or 24 Vdc
8
12
14
12
2
prom (not available to the pLAN)
optoinsulated input no. to
24 Vac/Vdc or 230 Vac (50/60 Hz)
none
2
4
inputs
8
14
18