Riello START 28 KI Manuel D'installation Et D'utilisation page 6

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

START KI - KIS
When necessary, the flue gas flange (A), must be removed or replaced
using a screwdriver as a lever.
In this case, the combustion supporting air is taken from the
room in which the boiler is installed, which must be a suitable
and ventilated technical room.
Non-insulated fumes outlet ducts are potential sources of danger.
It is appropriate to install a condensate collector and specific
pipes. In this case realize an inclination of 3° to the condensate
collector.
24 KIS
Max length fumes
outlet duct Ø 80 mm
up to 2m
from 2m to 8m
from 8m to 25m
28 KIS
Max length fumes
outlet duct Ø 80 mm
up to 4m
from 4m to 9m
from 9m to 15m
from 15m to 21m
35 KIS
Max length fumes
outlet duct Ø 80 mm
up to 5m
from 5m to 12m
(*) fitted in the boiler
"SEALED" INSTALLATION (TYPE C)
The boiler must be connected to concentric or twin fumes discharge
and air intake ducts which must both be taken outside. Do not use
the boiler without them.
Concentric outlets (ø 60-100, fig. 10d)
The concentric outlets can be placed in the most suitable direction
according to room requirements.
For installation, follow the instructions supplied with the kit.
When necessary, the flue gas flange (A), must be removed or replaced
using a screwdriver as a lever.
It is appropriate to install a condensate collector and specific
pipes. In this case realize an inclination of 3° to the condensate
collector.
24 KIS
Max linear length
concentric
duct Ø 60-100 mm
up to 0,85m
from 0,85m to 2,35m
from 2,35m to 4,25m
28 KIS
Max linear length
concentric
duct Ø 60-100 mm
up to 0,85m
from 0,85m to 1,70m
from 1,70m to 2,70m
from 2,70m to 3,40m
35 KIS
Max linear length
concentric
duct Ø 60-100 mm
up to 0,85m
from 0,85m to 2,3m
(*) fitted in the boiler
6
Load losses
Flue gas
flange (ø)
45° bend
42
44 (*)
1,2m
not installed
Load losses
Flue gas
flange (ø)
45° bend
43
45 (*)
1,2m
47
not installed
Load losses
Flue gas
flange (ø)
45° bend
49 (*)
1,2m
not installed
Load losses
Flue gas
flange (ø)
45° bend
42
44 (*)
1,0m
not installed
Load losses
Flue gas
flange (ø)
45° bend
43
45 (*)
1,0m
47
not installed
Load losses
Flue gas
flange (ø)
45° bend
49 (*)
1,0m
not installed
Concentric outlets (ø 80-125, fig. 10g)
The boiler has been designed to be connected to concentric outlet/
suction pipes and with the opening for air suction closed.
The concentric outlets can be placed in the most suitable direction
according to room requirements, complying with the maximum lengths
indicated in the table.
For installation, follow the instructions supplied with the kit.
To go through the wall, drill a hole of Ø 130 mm.
According to the length of the pipes used, it is necessary to insert a
flange selecting from those contained in the boiler.
Pay special attention to external temperature and pipe length. Refer
to the diagram (fig. 10h) in order to establish if it is compulsory or not
to use a condensation collector. In case of operation at temperature
90° bend
lower than 60 °C, it is compulsory to use a condensation collector. If
a condensation collector is used, provide a slope of the flue exhaust
pipe of 3° towards the collector.
1,7m
Connect the condensation trap syphon to a white water outlet pipe.
Non insulated outlet pipes are potential sources of danger.
24 KIS
Max linear length
90° bend
concentric duct
Ø 80-125 mm
from 0,96 to 3,85 m
1,7m
from 3,85 to 7,85 m
from 7,85 to 12,4 m
28 KIS
Max linear length
concentric duct
90° bend
Ø 80-125 mm
1,7m
from 0,96m to 2,9m
from 2,9m to 5,20m
from 5,20m to 7,10m
from 7,10m to 10m
35 KIS
Max linear length
concentric duct
Ø 80-125 mm
from 0,96m to 2m
from 2m to 5,85m
(*) fitted in the boiler
If it is necessary to install the boiler on systems already existing (replacement
types Residence KIS), there is a "reduced concentric bend kit" available that
allows positioning the boiler by keeping the same flue gas hole.
90° bend
1,5m
Pipe length with
reduced bend
90° bend
(m)
up to 1,85
from 1,85 to 4,25
1,5m
Twin outlets (ø 80, fig. 10e)
Twin outlets can be placed in the most suitable direction according to
the room requirements.
Remove the closure plug secured with the screws and use the specific
90° bend
adaptor for the combustion air intake pipe (E).
The air inlet adaptor ø 80 (E) must be correctly directed, it is
1,5m
necessary to fasten it with the appropriate screws, so that the
positioning flap does not interfere with the shell.
When necessary, the flue gas flange (A), must be removed using
a screwdriver as a lever. The table indicates the permitted linear
lengths. According to the length of the pipes used, it is necessary to
insert a flange, selecting one from those contained in the boiler (see
the following table).
Flue gas
flange (ø)
45° bend
42
44 (*)
not installed
Flue gas
flange (ø)
45° bend
43
45 (*)
47
not installed
Flue gas
flange (ø)
45° bend
49 (*)
not installed
START 24 KIS - reduced concentric bend
Flue gas
Load losses fort esch
flange (A)
45°
Ø 44 (**)
1
not installed
Load losses
90° bend
1,35m
2,2m
Load losses
90° bend
1,35m
2,2m
Load losses
90° bend
1,35m
2,2m
bend (m)
90°
1,5

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Start 24 kisStart 28 kisStart 35 kis

Table des Matières