4.2
CLEARANCES REQUIRED FOR SERVICING- Fig. 15
4.2.1. CLEARANCES REQUIRED FOR CLOSET INSTALLA-
TION
4.2.2. CLEARANCES FOR COMBUSTIBLES
Top and botton 0 in / 0 mm with a fi re-
resistant material betwenn the boiler
and the combustibles material.
IMPORTANT:
• The boiler must not be installed on carpeting.
• Keepeng boiler area clear and free from fl ammable vapors and
liquid.
13.58 in /
345 mm
30.04 in / 763 mm
Minimum
clearance of
17.71 in / 450 mm
from front of
boiler
Espace minimal
de 17.71 in / 450
mm du devant de
la chaudière
Fig. 15
1.77 in /
45 mm
Fig. 16
1.77 in / 45 mm
Fig. 17
4.2
ESPACES NÉCESSAIRES POUR L'ENTRETIEN - Fig. 15
8.66 in / 220 mm
17.72 in /
1.77 in / 45 mm
450 mm
9.84 in / 250 mm
4.2.1. ESPACES NÉCESSAIRES POUR L'INSTALLATION DANS
UN DEBARRAS
1.77 in /
45 mm
1.57 in /
40 mm
4.2.2. ESPACES LAISSÉS POUR DES COMBUSTIBLES
17.72 in /
1.77 in / 45 mm
450 mm
IMPORTANT:
• N'installez pas la chaudière sur un tapis ou une moquette.
• Ne stockez pas de produits infl ammables à proximité de la chaudière.
19
Minimum
clearances
Espaces mini-
maux
1.77 in / 45 mm
Sommet et fond 0" (pouces) / 0
mm avec un matériel résistant au
feu, entre le ballon et les matériaux
combustibles.