Gossen MetraWatt SINEAX DME 440 Mode D'emploi page 33

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Fig. 8 shows the connection of transducers DME 440 to the
MODBUS. The RS 485 interface can be realized by means of
PC built-in interface cards or interface converters. Both is
shown using i.e. the interfaces 13601 and 86201 of W & T
(Wiesemann & Theis GmbH). They are configured for a 2-wire
application with automatic control of data direction. These
interfaces provide a galvanical isolation and a built-in
termination network.
Important:
– Each device connected to the bus must have a unique
address (1 to 247, default ex factory: 247).
– All devices must be adjusted to the same baudrate.
33

Publicité

Table des Matières
loading

Table des Matières