Operating Instructions
Programmable multi-transducer SINEAX DME 440
Contents
12. Safety notes .............................................................. 39
1. Read first and then ...
The proper and safe operation of the device
assumes that the Operating Instructions are
read and the safety warnings given in the
sections
4. Physical installation
5. Electrical connections
7. Commissioning
12. Safety notes
are observed.
The device should only be handled by appropriately
trained personal who are familiar with it and authorized to
work in electrical installations.
2. Scope of supply (Figs. 1, 2, 3 and 4)
Fig. 1
Betriebsanleitung
Programmierbarer Multi-Messumformer
SINEAX DME 440
Mode d'emploi
Convertisseur de mesure multiple
programmable SINEAX DME 440
Operating Instructions
Programmable multi-transducer
SINEAX DME 440
DME 440-1 B d-f-e
127 127
01.99
Aargauerstrasse 7
CH-5610 Wohlen/Switzerland
Telefon +41 56 618 21 11
Telefax +41 56 618 24 58
Camille Bauer AG
Telex 827 901 cbm ch
Fig. 2
28
A
15+ 16-
B
17+ 18-
C
19+ 20-
D
21+ 22-
RS485
1:
23
Tx+/Rx+
25
GND
2:
MODBUS
24
Tx-/Rx-
26
000
3:
4:
Fig. 3
Fig. 4
Transducer (Fig. 1)
1 Operating Instructions (Fig. 2) in three languages:
German, French, English
1 blank type label (Fig. 3), for recording programmed settings
1 Interface definition DME 440 (Fig. 4)
3. Brief description
SINEAX DME 440 is a programmable transducer with a
RS 485 bus interface (MODBUS
variables of an electrical power system simultaneously and
generates 4 proportional analogue output signals.
The RS 485 interface enables the user to determine the
number of variables to be supervised (up to the maximum
available). The levels of all internal energy meters that have
been configured (max. 4) can also viewed. Provision is made
for programming the SINEAX DME 440 via the bus. A standard
EIA 485 interface can be used.
The transducers are also equipped with an RS 232 serial
interface to which a PC with the corresponding software can
be connected for programming or accessing and executing
useful ancillary functions. This interface is needed for bus
operation to configure the device address, the Baud rate and
possibly increasing the telegram waiting time (if the master is
too slow) defined in the MODBUS
The usual methods of connection, the types of measured
variables, their ratings, the transfer characteristic for each
output and the type of internal energy meters are the main
parameters that can be programmed.
The ancillary functions include a power system check,
provision for displaying the measured variable on a PC
monitor, the simulation of the outputs for test purposes and
a facility for printing nameplates.
4. Physical installation
The transducer can be mounted either on a top-hat rail or
directly onto a wall or mounting surface.
Note "Environmental conditions" in Section
"7.1 Technical data" when determining the place
of installation!
4.1 Mounting on top-hat rails
Simply clip the device onto the top-hat rail (EN 50 022) (see
Fig. 5).
®
). It supervises several
®
protocol.
Fig. 5. Mounting on top-hat rail
35 × 15 or 35 × 7.5 mm.