RAYSTAT-EX-02
ENGLISH
Installation instructions for nVent RAYCHEM
RAYSTAT-EX-02.
This thermostat is suitable for installation
where the following are applicable:
Circuit rating
< 22 A switching current
480 V
Hazardous area coding
LCIE 08 ATEX 6095X
II 2 G D
Ex db IIC T6 Gb
Ex tb IIIC T80°C Db IP66
IECEx LCI 08.0036X
Ex db IIC T6 Gb
Ex tb IIIC T80°C Db IP66
–40˚C < Ta < +60˚C
N°: 09-IEx-0009X
Ex d IIC T6 Gb
Ex tb IIIC T80°C Db IP66
TC RU C-BE.ИМ43.B.01764
1Ex d IIC T6 Gb X
Ex tb IIIC T80°C Db X
Ta -40°C...+60°C IP65
ООО "ТехИмпорт"
Special conditions for Safe Use:
According to IEC/EN 60079-1 regarding
thread maintenance applies: the
flamepaths are specified with maximum
gaps smaller than those shown in the
standard and shall not be enlarged. The
manufacturer should be consulted for
values if required for mainenance.
Ta = Ambient Temperature
To complete the heating cable system
other components must be selected
from the nVent literature.
Segurança
Follow instructions carefully.
the requirements of the relevant
European Directives.
For cable connection in hazardous area
verify that the proper type gland is used!!
(IEC /EN 60079-14 §10.4.2 d or e).
Zone 1 or Zone 2, Gas group IIC:
use flameproof cable entry devices
incorporating compound filled seals
around the individual cores or another
suitably certified sealing arrangement.
In all other cases use for armored cable
GL-33 and for non-armored power cables
GL-34.
WARNING:
DO NOT OPEN WHILE ENERGIZED
Only use copper conductors suitable
for 90°C
Declaration of
conformity
Our products satisfy
nVent.com | 5