Configuring Alarms
The IAQ Probe is configured with default alarm levels. However, it is
possible to modify the alarm settings to suit specific needs.
1
Press Mode/ESC to access the main menu.
2
Use the arrows to scroll to Alarm and press
Enter to select.
3
Use the arrow keys to display either the CO
or CO sensor press Enter to select.
4
Use the arrows to display either LOW or
HIGH and press Enter to select. (The
concentration level flashes to indicate that it may be modified.)
5
Use the arrows to change the alarm value (increase or decrease)
and press Enter to confirm.
6
Repeat steps 3 to 5 for the other alarm level.
7
Repeat steps 3 to 6 for the other sensor.
8
Press Mode/ESC to exit the menu.
22
IAQ Probe User Manual
Honeywell
2
ALARM
HIGH
MODE
Alarm
511403
2/07