Param-
Description
eter
1=invert the
direction of
rotation
MIN.FR
Minimum
EQ
start-up and
stop frequen-
cy of the mo-
tor. Frequen-
cy at which
the converter
begins to run
(upon start-up
and shut-
down) without
using the
ramps.
EXT.LO
Enable the
W WA-
digital input
TER
and connect
the level sen-
sor to ensure
that the pump
stops when
there is no
water. See
(refer to figure
5.7). Alarm
A1 if parame-
ter EXT.LOW
WATER=YES
and the elec-
trical contact
is open.
SET
Set the re-
PRESS
quired pres-
sure value of
the system
(set point)
MIN.PR
Pressure val-
ESS
ue of the sys-
tem below
which the A4
"minimum
pressure"
alarm is trig-
gered. When
the alarm is
triggered, the
pump stops
and the ART
function is en-
abled. See
Special func-
tions
on page
39. Trigger-
ing of the
alarm is de-
layed by the
Range Unit of
Default
meas-
ure-
ment
15–45,
Hz
30
three-
phase
motor
20–45,
single-
phase
motor
NO:
-
NO
Disa-
bled, no
control
YES:
Ena-
bled
0.0–10
bar
2.5
0.0–16
(in rela-
tion to
the full
scale of
the
sensor)
0.0–
bar
0.0
(SET
PRESS
-0.4)
0.0 =
Disa-
bled
Param-
Description
eter
length of time
set in the MP
TIMER pa-
rameter.
MP DE-
Delay for di-
LAY
agnosing the
MIN.PRESS
condition
P.SEN-
Pressure sen-
SOR
sor used
START
This parame-
VALUE
ter is the val-
ue for starting
the pump af-
ter a stop, cal-
culated as a
percentage of
the required
set point val-
ue.
Example:
SET PRESS=
4.0bar
START VAL-
UE=90% (3.6
bar)
If the pres-
sure in the
system reach-
es the re-
quired pres-
sure of 4.0
bar and there
is no addition-
al consump-
tion, the con-
verter disa-
bles the
pump. As
consumption
increases and
the pressure
decreases,
the converter
turns on the
pump when
the pressure
falls below the
START VAL-
UE of 3.6 bar.
5.3.2 Advanced menu (ME) parameters
In MANUAL mode and with the LED (10) off:
1. Press and hold (3) and (6) at the same time for
a few seconds. The LED (10) flashes.
2. Press (4) and (5) to edit the value of the param-
eter.
en - Original instructions
Range Unit of
Default
meas-
ure-
ment
1–99
sec
20
0–10
bar
0–16
0–16
0–99
%
90
37