3.4
POSITIONING AND CONNECTION OF THE BATTERIES
Risk of electric shock
A battery can present a risk for electrical shock and high short circuit current. The
following precautions should be observed when working on batteries:
a)
Remove watches, rings or other metal objects;
b)
Use tools with insulated handles;
c)
Wear rubber gloves and boots;
d)
Do not lay tools or metal parts on top of batteries;
e)
Disconnect the charging source prior connecting or disconnecting battery
terminals;
f)
Determine if battery is inadvertently grounded. If inadvertently grounded,
remove source from ground. Contact with any part of a grounded battery can
result in electrical shock. The likelihood of such shock can be reduced if
such grounds are removed during installation and maintenance (applicable
to equipment and remote battery supplies not having a grounded supply
circuit).
Follow the installation instructions
For battery installation please respect EN62040-1 strictly and follow the installation
manual of the UPS.
To obtain the battery life indicated by the battery manufacturer, the operating
temperature must remain between 0 and 25 °C. However, although the battery can
operate up to 40°C, there will be a significant reduction of the battery life.
To avoid the formation of any kind of potentially explosive hydrogen and oxygen
mixture, suitable ventilation must be provided where the battery is installed (see
EN62040-1 annex M).
For the materials installed in France, the rule stated by NFC 15-100 article 554.2
must be applied: the volume of the renewed air has to be at least 0,05 NI m
hour, where N is the number of the elements inside the battery and I is maximum
current of the rectifier.
The batteries can either be internal or external; it is recommended to install them when the UPS is
capable of charging them. Please remember that, if the battery is not charged for periods over 2-3
months it can be subject to irreparable damage.
Auxiliary contact of the external battery switch
For a correct operation of the UPS it is advisable to connect the auxiliary contact of
the external battery switch to the terminals X10-9/10.
28
OMT87187 REV. A
Installation and start-up of KEOR HPE UPS 400-500 kVA
Installation et démarrage de l'ASI KEOR HPE 400-500 kVA
Installazione e avviamento KEOR HPE UPS 400-500 kVA
3
per