Installation and start-up of KEOR HPE UPS 400-500 kVA
Installation et démarrage de l'ASI KEOR HPE 400-500 kVA
Installazione e avviamento KEOR HPE UPS 400-500 kVA
Picture 22 – Opening the manual bypass switch
Picture 23 – Inverter start-up
5)
As soon as the inverter is started it will be possible to transfer the load. Move the bypass
switch as required by the display to complete the UPS start-up.
OMT87187 REV. A
49