Alarm
Description
Possible
causes
Solutions
Alarm
Description
Possible
causes
Solutions
Alarm
Description
Possible
causes
Solutions
Alarm
Description
Possible
causes
Solutions
52
OMP06263 REV. B
UPS user manual
Manuel de l'utilisateur de l'ASI
Utilizzo dell'UPS
A9
BATTERY AUTONOMY END
The battery has reached the pre-alarm discharge level.
 The battery is discharging due to a mains failure.
 Rectifier failure.
1. Check which alarms are present and carry out the indicated
procedures.
2. If the alarm persists, contact our Technical Support Service.
A10
BATTERY FAULT
Fault following a battery test.
 Battery fault.
1. Check the battery.
2. Reset the system.
3. If the alarm persists, contact our Technical Support Service.
A11
SHORT CIRCUIT
The current sensor has detected a short-circuit at the output.
 Load problem.
 Measuring circuit failure.
1. Check the loads connected to the UPS output.
2. If the alarm persists, contact our Technical Support Service.
A12
STOP TIMEOUT SHORT-CIRCUIT
Inverter shutdown due to an extended short-circuit during a power
failure, or due to an overcurrent on the inverter bridge input.
 Short-circuit on the loads during a power failure.
 Inverter bridge fault.
 Temporary current peak.
1. Reset the system.
2. If the alarm persists, contact our Technical Support Service.